GEK-105593C
41
•
Accuracy:
-Voltage and current
5%
-Timers
5% or 30ms (whichever is greater)
- Error index
Class E-5 as per IEC 255-4
•
Repetitivity
-Operating value
1%
-Operating time
2% or 30ms (whichever is greater)
COMMUNICATIONS
- RS232 using DB9 female connector (2 or 3 connectors depending on model)
- Mode : Half duplex.
- 1 mm plastic fiber-optic (depending on model)
Typical power output :
-8 dBm
Receiver sensitivity
-39 dBm
Numeric aperture N.A.
0.5
Wave length
660 nm (visible red)
HFBR-4516 type connector
- Glass fiber-optic 62.5/125 (depending on model):
Typical power output:
-17.5 dBm
Receiver sensitivity
-25.4 dBm
Numeric aperture N.A.
0.2
Wave length
820 nm (near infrared)
SMA type connector
STANDARDS
The SMOR system complies with the following standards, which include the GE insulation and
electromagnetic compatibility standard and the standards required by Community Directive 89/336 for the EC
market, in line with European standards. It also complies with the European directive requirements for low
voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC 255-
5, IEC 255-6 and IEC 68.
Test
Standard
Class
•Insulation test voltage
IEC 255-5
600V, 2kV
50/60Hz 1min.
•Impulse Voltage Withstand
IEC 255-5
5kV,0.5 J
•1 MHz interference
IEC 255-22-1
III
•Electrostatic discharge
IEC 255-22-2
IV
EN 61000-4-2
8kV
•Immunity to radio interference
IEC 255-22-3
III
•Electromagnetic fields radiated with
ENV 50140
10 V/m
amplitude modulation
•Electromagnetic fields radiated with
ENV 50141
10 V/m
amplitude modulation. Common mode
•Electromagnetic fields radiated with
ENV 50204
10 V/m
frequency modulation
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...