GE Power Management
SMOR_B 1000/7000 QUICK REFERENCE GUIDE
Description
User
Limits
COMMON SETTINGS TO ALL TABLES
General Settings Group
RELAY STATUS
In/Out of service
IDENTIFICACION
20 ASCII characters
RATED VOLTAGE (PH-PH)
90-200
FREQUENCY
50/60 Hz
CT PHASE RATIO
1-4000
CT GROUD RATIO
1-4000
VT LINE RATIO
1-4000
*
VT BUSBAR RATIO
1-4000
DEMAND TIME
15/30/60 min
PHASE ROTATION SELECTION
ABC/CBA
Breaker Settings Group
BREAKER NUMBER
4 ASCII characters
FAIL TO OPEN TIME
0.05
-1
sg
.
FAIL TO CLOSE TIME
0.05
-5
sg
.
ACCUMULABLE I2t LIMIT
1-999999 kA
2
s
INTG.
I2t TIME SELECTOR
Fixed / Measured
I2t INTEGRATION TIME
0.03
-0.25
sg
.
MAXIMUM TRIPS IN 1 HOUR
1-50
Active Table Settings Group
# OF ACTIVE SETTINGS TABLE
1-3
COLD PICK-UP PERMISSION
No / Yes
CHANGE TO TABLE 3 TIME
Max.
Reclose time/240
sg.
RETURN FROM TABLE 3 TIME
Safety Time / 1800
sg.
Oscillography Mask Settings Group
NUMBER OF PRE-FAULT CYCLES
2-10
PICK-UP 51 PT
Enabled/Disabled
PICK-UP 51 NT
Enabled/Disabled
PICK-UP 50
PH
Enabled/Disabled
PICK-UP 50 PL
Enabled/Disabled
PICK-UP 50 NH
Enabled/Disabled
PICK-UP 50 NL
Enabled/Disabled
PICK-UP 46 PT
Enabled/Disabled
PICK-UP 81 0
Enabled/Disabled
PICK-UP 81 U
Enabled/Disabled
PICK-UP 27 P
Enabled/Disabled
PICK-UP 59 P
Enabled/Disabled
PICK-UP 59 NH
Enabled/Disabled
PICK-UP 59 NL
Enabled/Disabled
EXTERNAL TRIGGER
Enabled/Disabled
COMUNICATIONS TRIGGER
Enabled/Disabled
TRIP 51 PT
Enabled/Disabled
TRIP 51 NT
Enabled/Disabled
TRIP 50
PH
Enabled/Disabled
TRIP 50 PL
Enabled/Disabled
TRIP 50 NH
Enabled/Disabled
TRIP 50 NL
Enabled/Disabled
TRIP 46 PT
Enabled/Disabled
TRIP 81 0
Enabled/Disabled
TRIP 81 U
Enabled/Disabled
TRIP 27 P
Enabled/Disabled
TRIP 59 P
Enabled/Disabled
TRIP 59 NH
Enabled/Disabled
TRIP 59 NL
Enabled/Disabled
Function Permission Settings Group
51 PT FUNCTION PERMISSION
Not allowed/Allowed
51 NT FUNCTION PERMISSION
Not allowed/Allowed
50
PH FUNCTION PERMISSION
Not allowed/Allowed
50 PL FUNCTION PERMISSION
Not allowed/Allowed
50 NH FUNCTION PERMISSION
Not allowed/Allowed
* Disregard for SMOR7000
Description
User
Limits
50 NL FUNCTION PERMISSION
Not allowed/Allowed
46 PT FUNCTION PERMISSION
Not allowed/Allowed
81 O FUNCTION PERMISSION
Not allowed/Allowed
81 U FUNCTION PERMISSION
Not allowed/Allowed
27 P FUNCTION PERMISSION
Not allowed/Allowed
59 P FUNCTION PERMISSION
Not allowed/Allowed
59 NH FUNCTION PERMISSION
Not allowed/Allowed
59 NL FUNCTION PERMISSION
Not allowed/Allowed
51 PT TRIP PERMISSION
Enabled/Disabled
51 NT TRIP PERMISSION
Enabled/Disabled
50
PH TRIP PERMISSION
Enabled/Disabled
50 PL TRIP PERMISSION
Enabled/Disabled
50 NL TRIP PERMISSION
Enabled/Disabled
50 NH TRIP PERMISSION
Enabled/Disabled
46 PT TRIP PERMISSION
Enabled/Disabled
81 O TRIP PERMISSION
Enabled/Disabled
81 U TRIP PERMISSION
Enabled/Disabled
27 P TRIP PERMISSION
Enabled/Disabled
59 P TRIP PERMISSION
Enabled/Disabled
59 NH TRIP PERMISSION
Enabled/Disabled
59 NL TRIP PERMISSION
Enabled/Disabled
INDEPENDENT SETTINGS FOR EACH TABLE
51 PT Function Settings Group
51 / 67 P PICK-UP
1.00-12.00 A
CURVE
Inv./M Inv./E Inv./
Def. Time
TIME DIAL
0.05-1.00
DEFINITE TIME SETTING
0.00-100.00
sg
51 NT Function Settings Group
51 / 67 N PICK-UP
0.20-2.40 A
CURVE
Inv./M Inv./E Inv./
Def. Time
TIME DIAL
0.05-1.00
DEFINITE TIME SETTING
0.00-100.00
sg
50
PH Function Settings Group
50 / 67 P PICK-UP
1.00-160.00 A
TIME DELAY
0.00-60.00
sg
50 PL Function Settings Group
50 / 67 P PICK-UP
1.00-160.00 A
TIME DELAY
0.00-60.00
sg
50 NH Function Settings Group
50 / 67 N PICK-UP
0.20-32.00 A
TIME DELAY
0.00-60.00
sg
50 NL Function Settings Group
50 / 67 N PICK-UP
0.20-32.00 A
TIME DELAY
0.00-60.00
sg
46 PT Function Settings Group
51 / 67 N PICK-UP
0.10-4.00 A
CURVE
Inv./M Inv./E Inv./
Def. Time
TIME DIAL
0.05-1.00
DEFINITE TIME SETTING
0.00-100.00
sg
81 Function Settings Group
81 U PICK-UP
40.00-70.00 Hz
UNDERFREQUENCY TIME DELAY
0.00-100.00
sg
81 O PICK-UP
40.00-70.00 Hz
OVERFREQUENCY TIME DELAY
0.00-100.00
sg
UNDERVOLTAGE SUPERVISION
40-110 %
Voltage Settings Group
UNDERVOLTAGE PICK-UP (27 P)
10.00-260.00 V
27 P TIME DELAY
0.03-100.00
sg
OVERVOLTAGE PICK-UP (59 P)
10.00-260.00 V
59 P TIME DELAY
0.03-100.00
sg
Description
User
Range
OVERVOLTAGE PICK-UP (59 NH)
3.00-100.00 V
59 NH TIME DELAY
0.03-100.00
sg
OVERVOLTAGE PICK-UP (59 NL)
3.00-100.00 V
59 NL TIME DELAY
0.03-100.00
sg
Directionality Settings Group
51 PT DIRECTIONAL
Not allowed/Allowed
51 NT DIRECTIONAL
Not allowed/Allowed
50
PH DIRECTIONAL
Not allowed/Allowed
50 PL DIRECTIONAL
Not allowed/Allowed
50 NH DIRECTIONAL
Not allowed/Allowed
50 NL DIRECTIONAL
Not allowed/Allowed
CHARACTERISTIC ANGLE – PHASE
-90.00º - +90.00º
CHARACTERISTIC ANGLE – GROUND
-90.00º - +90.00º
LOSS VOLTAGE LOGIC
Block/Permission
Recloser Settings Group
RECLOSER PERMISSION
Not allowed/Allowed
NUMBER OF CYCLES
1-4
RESET TIME
0-600
sg
HOLD MODE SELECTION
NO/YES
HOLD MODE TIME
0-100
sg
1
ST
RECLOSE TIME
0.10-100.00
sg
2
ND
RECLOSE TIME
0.10-100.00
sg
3
RD
RECLOSE TIME
0.10-100.00
sg
4
TH
RECLOSE TIME
0.10-100.00
sg
RECLOSE CONDITIONS
0-4
0-No Condition 1-Inhib. Input
*
2-Voltage only on
*
3-Voltage on
busbar
*
4-Voltage on both sides
RECLOSE PERMISSION AFTER 51 PT
Enabled/Disabled
RECLOSE PERMISSION AFTER 51 NT
Enabled/Disabled
RECLOSE PERMISSION AFTER 50
PH
Enabled/Disabled
RECLOSE PERMISSION AFTER 50 PL
Enabled/Disabled
RECLOSE PERMISSION AFTER 50 NH
Enabled/Disabled
RECLOSE PERMISSION AFTER 50 NL
Enabled/Disabled
RECLOSE PERMISSION AFTER 46 PT
Enabled/Disabled
RECLOSE PERMISSION AFTER 81 U
Enabled/Disabled
RECLOSE PERMISSION AFTER 81 O
Enabled/Disabled
RECLOSE PERMISSION AFTER 27 P
Enabled/Disabled
RECLOSE PERMISSION AFTER 59 P
Enabled/Disabled
RECLOSE PERMISSION AFTER 59 NH
Enabled/Disabled
RECLOSE PERMISSION AFTER 59 NL
Enabled/Disabled
RECLOSE PERMISSION WITH AN INPUT
Enabled/Disabled
TRIP PERMISSION 51 PT AFTER 79
Enabled/Disabled
TRIP PERMISSION 51 NT AFTER 79
Enabled/Disabled
TRIP PERMISSION 50
PH AFTER 79
Enabled/Disabled
TRIP PERMISSION 50 PL AFTER 79
Enabled/Disabled
TRIP PERMISSION 50 NH AFTER 79
Enabled/Disabled
TRIP PERMISSION 50 NL AFTER 79
Enabled/Disabled
TRIP PERMISSION 46 PT AFTER 79
Enabled/Disabled
TRIP PERMISSION 81 U AFTER 79
Enabled/Disabled
TRIP PERMISSION 81 O AFTER 79
Enabled/Disabled
TRIP PERMISSION 27 P AFTER 79
Enabled/Disabled
TRIP PERMISSION 59 P AFTER 79
Enabled/Disabled
TRIP PERMISSION 59 NH AFTER 79
Enabled/Disabled
TRIP PERMISSION 59 NL AFTER 79
Enabled/Disabled
NOTE:
Pick-up settings correspond to a range C relay:
1 - 12 A
Phases
0.2 - 2.4 A
Ground
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...