GEK-105593C
52
PHASE CURRENTS
•
Inject the following current values into the relay:
I (Amp)
Angle
1
2
3
4
Ia
45
0.1xIn
0.5xIn
1xIn
2xIn
Ib
165
0.1xIn
0.5xIn
1xIn
2xIn
Ic
285
0.1xIn
0.5xIn
1xIn
2xIn
(In is the nominal or rated current for the relay phase current inputs, 5 or 1 Amp)
•
Check that the relay measures Ia, Ib, Ic with an accuracy of at least 5%.
•
Repeat the test for 60 Hz.
GROUND CURRENTS
•
Inject the following current values into the relay:
I (Amp)
Angle
1
2
3
4
Iground
0
0.1xIn(gnd)
0.5xIn(gnd)
1xIn(gnd)
5xIn(gnd)
(In is the nominal or rated current for the relay ground current input, 5 or 1 Amp)
•
Check that the relay measures Iground with an accuracy of at least 5%.
•
Repeat the test for 60 Hz.
6.10.2. FREQUENCY MEASUREMENT
•
Apply 110V at 50 Hz through the voltage input corresponding to phase B.
•
Check that the frequency measured by the relay is inside the range of 49.97 and 50.03 Hz.
NOTE : Check that the inhibition voltage of the frequency units is lower than the applied voltage. If not, the
unit does not measure the frequency.
6.11. RECLOSER
Recloser Settings Group
79 Status
Permitted
Number of cycles
4
Reset Time
10 sec
Hold Mode
NO
Hold Timer
15 sec
1st Reclose Delay
2.1 sec
2nd Reclose Delay
4.1 sec
3rd Reclose Delay
6.1 sec
4th Reclose Delay
8.1 sec
Recl. Conditions
Inh. Input
Enable only 51PL function, and set its pick up and timer to the minimum value possible.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...