Apply 36 Vac on phase B, at a frequency of 54 Hz. The relay should not trip, due to the voltage
supervision.
6.22. UNDERVOLTAGE UNIT (27)
•
Enable only 27P function and its related trip.
•
Set the relay as follows:
27/’59 Functions Settings Group
27P Pick up
10 V (ph-ph) (5.77 V ph-gnd)
Time Delay 27P
0.20 sec
•
Apply on the three phases of the relay 6.4 Vac and check that the relay does not trip.
•
Apply 5.2 Vac and check that the relay trips.
•
Check that for this trip, the operating time is in between 0.18 and 0.22 sec.
•
Set the relay as follows:
27/’59 Functions Settings Group
27P Pick up
100 V (ph-ph) (57.7 V ph-gnd)
Time Delay 27P
4.0 sec
•
Apply on the three phases of the relay 60.5 Vac and check that the relay does not trip.
•
Apply 54.8 Vac and check that the relay trips.
•
Check that for this trip, the operating time is in between 3.9 and 4.1 sec.
6.23. OVERVOLTAGE UNIT (59)
•
Enable only 59P function and its related trip.
•
Set the relay as follows:
27/’59 Functions Settings Group
59P Pick up
10 V (ph-ph)
Time Delay 59P
0.20 sec
•
Apply on phase A of the relay 9 Vac and check that the relay does not trip.
•
Apply 11 Vac and check that the relay trips.
•
Check that for this trip, the operating time is in between 0.18 and 0.22 sec.
•
Set the relay as follows:
27/’59 Functions Settings Group
27P Pick up
100 V (ph-ph) (57.7 V ph-gnd)
Time Delay 27P
4.0 sec
•
Apply on phase A of the relay 95 Vac and check that the relay does not trip.
•
Apply 105 Vac and check that the relay trips.
•
Check that for this trip, the operating time is in between 3.9 and 4.1 sec.
•
Repeat both tests for phases B and C.
6.24. ZERO SEQUENCE OVERVOLTAGE UNIT, HIGH LEVEL (59 NH)
•
Enable only 59NH function and its related trip.
•
Set the relay as follows:
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...