GEK-105593C
51
•
Set the Failure to close timer to the maximum. Perform a closing command and check that during the
failure to open time the Reclose-1 (C1-D1) and Reclose-2 (C2-D2) output contacts are closed.
•
Enable only 51P function, and set it to its minimum value. Inject a current to phase A equal to 2xIn(phase)
to trip the relay. Check that S1 auxiliary output (C4-C6) closes and also S9 (E1-F1) if an expansion board
exists.
•
Enable only 51N function, and set it to its minimum value. Inject a current to the ground input equal to
2xIn(ground) to trip the relay. Check that S2 auxiliary output (D4-C6) closes and also S11 (E3-F3) if an
expansion board exists.
•
Enable only 46 function, and set it to its minimum value. Inject a current to phase A equal to 2xIn(phase)
to trip the relay. Check that S3 auxiliary output (C5-C6) closes.
•
Enable only 81O function, and set it to its minimum value. Inject nominal voltage on phase B voltage
input, at nominal frequency to trip the relay. Check that S4 auxiliary output (D5-C6) closes.
•
Enable only 59P function, and set it to its minimum value. Inject nominal voltage on phase A voltage
input, at nominal frequency to trip the relay. Check that S5 auxiliary output (C7-D6) closes.
•
With the recloser out of service check that output S8 (D8-D6) is closed. Set the recloser in service and
check the S8 opens. Set the recloser to one reclosing attempt with a 5 sec time delay, without reclosing
condition checking and a reset time equal to 10 sec. Enable only 51P function and make the relay to trip.
Check that S7 closes (C8-D6) during the 5 sec the recloser lasts. Before 10 sec make the relay to trip
again and check the recloser moves to the lockout status, closing output number S6 (D7-D6).
•
Remove the Power Supply to the relay and check that the Alarm contact (C3-D3) closes. Set the power
supply back to the relay and check that the Alarm contact opens.
6.10. CHECKING RELAY MEASUREMENTS
6.10.1. CURRENT AND VOLTAGE MEASUREMENT
•
Set the relay in the following way :
General Settings Group
Frequency
50 Hz
CT Phase ratio
1
CT Ground ratio
1
PT line phase ratio
1000
PT busbar phase ratio
1000
VOLTAGES
•
Apply the following voltage values to the relay :
V
Angle
1
2
3
4
5
6
Van
0
0
1
10
50
100
150
Vbn
120
0
1
10
50
100
150
Vcn
240
0
1
10
50
100
150
•
Check that the relay measures Vab, Vbc, Vac with an accuracy of at least 5%.
•
Repeat the test for 60 Hz.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...