GEK-105593C
40
4.2. TECHNICAL CHARACTERISTICS
MECHANICAL
•
Metal casing 19 inches rack case 2 units high
•
IP51 Grade Protection (as per IEC 529)
•
Local MMI with LCD screen consisting of 2 rows of 16 characters and 20 key keyboard
•
Rear connection by means of 4 strips of 12 terminals each (6 strips with optional I/O expansion board)
•
Dimensions : 437 x 164 x 88 mm
•
Weight: net 6 kg. Shipping 7 kg.
ELECTRICAL
•
Frequency:
50 or 60 Hz (selectable by setting)
•
Nominal current:
1 or 5 A (Different models)
•
Nominal voltage:
100/
√
3 to 220/
√
3 Vac
•
Auxiliary voltage:
48 Vdc or 110-250 Vdc (Different models)
•
Operational range
80% to 120% of nominal values
•
Digital input voltage:
48, 110-250 Vdc (Different models)
•
Thermal capacity:
Current circuits
- Permanent
4 x In
- 3 s duration
50 x In
- 1 s duration
100 x In
Voltage circuits
- Permanent
2 x Un
- 1 min. duration
3.5 x Un
•
Temperature ranges
- Operating
-20º C to + 55ºC
- Storage
-40ºC to + 65ºC
•
Humidity
Up to 95% without condensation
•
Tripping contacts:
- Rated voltage/Maximum opening voltage:
250/440 Vac
- Rated current/Closing current:
16/25 A
- Operating power:
4000 VA
- Mechanic life:
30 x 10
6
ops
•
Auxiliary & alarm contacts:
- Operating power:
4760 VA
- Operating voltage:
380/250 Vac/Vdc
- Continuous operating current
8 A
- Mechanic life:
10
7
ops
- Electrical life, full load:
10
5
ops
•
Circuits burden
- Current circuits
0.5 VA to In = 5 A
0.1 VA to In = 1 A and In = 0.2 A
- Voltage circuits:
0.2 VA to Un = 63.5 V
•
Consumption:
-Auxiliary voltage
12 W idle state
16 W all relays activated
-Digital inputs
8 mA (1 W for Vaux = 125 Vdc)
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...