GEK-105593C
53
6.11.1. CHECKING RECLOSER CYCLE
•
After setting the relay, close the Breaker and wait 10 sec. After this time the recloser is ready to start the
reclose cycle.
•
Force a 50 PL trip and check that relay recloses in 2.1 sec.
•
Before 10 sec force a 50 PL trip and check that relay recloses in 4.1 sec.
•
Before 10 sec force a 50 PL trip and check that relay recloses in 6.1 sec.
•
Before 10 sec force a 50 PL trip and check that relay recloses in 8.1 sec.
•
Before 10 sec force a 50 PL trip and check that the recloser goes to lockout, closing the auxiliary output
S6 (D7-D6).
6.11.2. CHECKING THE RECLOSER BLOCK
•
Close the breaker and wait 10 sec. After this time the recloser is ready to start a new reclosing cycle.
Energize input CC2 (D9-D10) (pulse signal) to block the recloser.
•
Force a 50PL trip and check the recloser does not reclose.
•
Close the breaker. Energize CC3 input (C10-D10) (pulse signal) to unblock the recloser. Force a 50PL
trip and check that the recloser closes in 2.1 sec.
6.11.3. CHECKING RECLOSER INHIBITION
•
Enable the Hold Mode in the recloser settings. Close the Breaker and wait 10 sec. After this time the
recloser is ready to start the reclosing cycle.
•
Force a trip and wait for the 1st reclose to take place.
•
Energize CC6 input (C12-D12) (Reclose inhibit) and force a 50 PL trip.
•
After 12 sec. de-energize CC6 input and check that at that moment the relay recloses.
•
Activate CC6 input (Reclose inhibit) and force a 50 PL trip.
•
After 18 sec de-energize CC6 input and check that the relay does not reclose. The recloser should be in
LOCKOUT.
6.11.4. CHECKING RECLOSE INITIATION
(Only for models with expansion board)
•
Close the Breaker and wait 10 sec. After this time the recloser is ready to start the reclosing cycle.
•
Force a 50PL trip and wait for the 1st reclose to take place.
•
Before 10 sec energize CC7 input (Reclose Initiation) and check that after 4.1 sec (corresponding to the
2nd reclose) the relay recloses again.
6.12. INSTANTANEOUS PHASE OVERCURRENT UNIT, HIGH LEVEL (50PH)
•
Enable only 50PH function and the related trip.
•
Set its time delay and pick up to the minimum possible.
•
With 0.9 times the pick up current the relay should not trip.
•
With 1.1 times the pick up current the relay should trip instantaneously in between 10 to 50 ms.
•
With 4 times the pick up current the relay should trip instantaneously in between 10 to 40 ms.
•
The test should be carried out for phases A, B and C.
6.13. INSTANTANEOUS PHASE OVERCURRENT UNIT, LOW LEVEL (50PL)
•
Enable only 50PL function and the related trip.
•
Set its time delay and pick up to the minimum possible.
•
With 0.9 times the pick up current the relay should not trip.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...