GEK-105593C
11
CLOSE CIRCUIT SUPERVISION
2.2.5. BREAKER HEALTH MONITORING
To supervise the breaker health, SMOR system calculates and stores, for each operation, the accumulated
values for the square of the current multiplied by the opening time of the breaker (
Σ
I2t) on each of the three
phases. If the nominal current is not exceeded, as is the case for a manual opening command with no fault
current, the relay uses the nominal current value instead of the measured value.
The value I2t is accumulated and stored independently for each phase. These values can be accessed
either by local MMI or by GE-LOCAL communication software.
The function has an "Integration Time Selector" setting which can be used to assign a fixed opening time
(given by another "Integration Time" setting). Otherwise it allows the unit to measure this time from the
moment the opening command is given until the moment when the breaker opens.
The "Accumulative Current Limit" setting establishes a threshold for the breaker's interruption capability (it is
advisable to set this to the limit supplied by the manufacturer). When this threshold is passed on any of the
three phases, the system gives an alarm. In addition, the system incorporates a counter for the number of
opening operations carried out.
The purpose of this function is to allow maintenance to be carried out in a more accurate method than using
fixed time periods. Once this maintenance operation has been carried out, the values for both the I2t and
number of opening operations, can be reset to zero.
In order to be able to take into account the history of the breaker, in the case where the breakers were
already in use before the installation of the relay, the system allows to set an initial value for the
Σ
I2t and the
number of opening operations carried out. Similarly, these values can be adjusted to a given value in order
to take into account the operations carried out during the protection testing.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...