GEK-105593C
61
•
Check on the relay that the number of opening operations is 2, and the number of accumulated amperes
is between 5700 and 6400 kA
2
s (exact value 6100) for In(phase) = 5 Amp.
6.27. COMMANDS.
•
The following tasks have to be carried out :
1. Breaker OPENING : Use communications to give a breaker opening command and check that the
breaker opens.
2. Breaker CLOSING. Use communications to give a breaker closing command and check that the breaker
closes.
3. SYNCHRONIZATION. Use communications to synchronize the relay with the date/time on the PC. Check
that the relay is indeed synchronized.
4. DELETE EVENTS. Use communications to erase all the events and check it has been done.
5. BLOCK THE RECLOSER:
- Use communications to block the recloser.
- Close the breaker and wait 10 sec. After this time the recloser is ready to initiate a reclosing cycle
(if it is not blocked).
- Force a trip and check that the relay does not reclose.
6.- UNBLOCK THE RECLOSER:
- With the recloser enabled, issue this command to the relay. This command cancels the previous
one (recloser block).
- Force a trip and check the relay recloses after 2 sec (corresponding to the first programmed
reclose).
6.28. PHASE ROTATION ABC - CBA
•
Set the relay for the phase sequence ABC.
•
Apply the following currents to the relay:
Ia = In (phase) at 0
°
Ib = In (phase) at -120
°
Ic = In (phase) at -240
°
•
Check that the relay reads these values correctly, and I2=0 Amps (negative sequence)
•
Set the relay for phase sequence CBA
•
Check that the relay reads the values correctly, but now I2=In (phase).
6.29. MONITORING TRIP CIRCUITS: UNDERVOLTAGE
(Only for models with expansion board)
COIL 1:
•
Apply nominal minimum voltage (38 Vdc for "A" models and 88 Vdc for "H" models) to the voltage
supervision input for coil 1. Positive is applied to terminal F5 and negative to terminal E6.
•
Check using GE_LOCAL software that the "Coil 1 DC Supply Failure" signal in the internal Status of the
relay is not active.
•
Remove the voltage applied to the above mentioned input.
•
The "Coil 1 DC Supply Failure" signal will become active.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...