GEK-105593C
80
Screen
Possible values
59NH PICKUP
YES - NO
59NL PICKUP
YES - NO
79 STATUS
IN /OUT OF SERVICE
PROTEC. STATUS
IN / OUT OF SERVICE
ACTIVE TABLE
1:TABLE 1: 2:TABLE 2 3:TABLE 3
STATUS 52
OPEN - CLOSE
DIRECTION A
PERMISSION - BLOCK
DIRECTION B
PERMISSION - BLOCK
DIRECTION C
PERMISSION - BLOCK
DIRECTION G
PERMISSION - BLOCK
REM CONNECTION
IN / OUT OF SERVICE
LOCAL CONNECTION
IN / OUT OF SERVICE
DATE / TIME STATUS
CORRECT
E2PROM COMM
CORRECT
COMM SETTINGS
USER - DEFAULT
PROTECTION LINK
YES - NO
DATE & TIME
(SHOWS DATE & TIME)
8.4. OPERATIONS GROUP.
This group allows you to operate the breaker from the keyboard, and also to block or unblock the recloser
and to synchronize the time on the unit. To access this group, press the ACT key when the SMOR is in the
stand-by screen. This takes you to the operations menu and shows the first item on the menu:
This shows that the first item on the operations menu is the function for entering the date and time for the
relay. When the UP/DOWN ARROW keys are pressed the rest of the items on the operations menu appear.
After locating the required operation use the ENT key to select it.
To avoid carrying out operations by mistake the keyboard program requires confirmation of the operation
selected. To confirm, press the 1/Y key and then ENT. To abort the operation press the 3/N key and then
ENT. Pressing CLR is the equivalent of pressing the 3/N key and then ENT, aborting the operation.
If the command is confirmed the result of the operation appears on the screen. With either ENT or CLR you
can accept this message and return to the operations menu.
By way of example, this would be the process for opening the breaker starting from the operations menu;
If the breaker had not opened the result of the operation shown on the screen would have been "NOT
PERFORMED".
The SMOR can perform the following operations:
•
Set date/time
•
Block recloser
•
Unblock recloser
•
Oscillography triggering
•
Reset current maximeter
SET
DATE/TIME
OPEN BREAKER
CONFIRM?
(Y/N)
ENT
1/Y
PERFORMED
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...