GEK-105593C
30
removed from the keyboard/display and communications software. To carry out these configurations the GE-
INTRO configuration software must be run.
The following settings are common to all tables:
TABLE 5. COMMON SETTINGS TO ALL TABLES
Description
Limits
Default
Interval
General Settings Group
Relay status
In/out of service
In service
NA
Identification
20 ASCII characters
No Id.
NA
Frequency
50 / 60 Hz
50 Hz
NA
Rated Voltage (ph-ph)
90-220
110
1
CT Phase Ratio
1-4000
1
1
CT Ground Ratio
1-4000
1
1
VT Line Ratio
1-4000
1
1
VT Busbar Ratio
1-4000
1
1
Demand Time
15/30/60 min
60 min
NA
Phase rotation selection
ABC / CBA
ABC
NA
Breaker Settings Group
Breaker Number
4 ASCII characters
0000
NA
Fail to Open time
0.05 - 1s
0.5s
0.01s
Fail to Close time
0.05 - 5s
1s
0.01s
Accumulable I2t Limit
1 - 999999 kA
2
s
99999 kA
2
s
1
Intg I2t Time selector
Fixed / measured
Fixed
NA
I2t Integr. time
0.03 - 0.25s
0.06s
0.01s
Maximum trips in 1 hour
1 - 50
50
1
Active Table Settings
# of Active Settings Table
1 - 3
1
1
Cold pick-up permission
NO/YES
NO
NA
Change to Table 3 time
Reclose time-240s
60s
1s
Return from Table 3 time
Reset
time-1800s
120s
1s
Oscillography Mask
Number of pre-fault cycles
2 - 10
2
1
Oscillo. triggers :
Pick-up 51 PT
Enabled/disabled
Enabled
NA
Pick-up 51 NT
Enabled/disabled
Enabled
NA
Pick-up 50 PH
Enabled/disabled
Enabled
NA
Pick-up 50 PL
Enabled/disabled
Enabled
NA
Pick-up 50 NH
Enabled/disabled
Enabled
NA
Pick-up 50 NL
Enabled/disabled
Enabled
NA
Pick-up 46 PT
Enabled/disabled
Enabled
NA
Pick-up 81 U
Enabled/disabled
Enabled
NA
Pick-up 81 O
Enabled/disabled
Enabled
NA
Pick-up 27 P
Enabled/disabled
Enabled
NA
Pick-up 59 P
Enabled/disabled
Enabled
NA
Pick-up 59 NH
Enabled/disabled
Enabled
NA
Pick-up 59 NL
Enabled/disabled
Enabled
NA
External Trigger
Enabled/disabled
Enabled
NA
Communications Trigger
Enabled/disabled
Enabled
NA
Trip 51 PT
Enabled/disabled
Enabled
NA
Trip 51 NT
Enabled/disabled
Enabled
NA
Trip 50 PH
Enabled/disabled
Enabled
NA
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...