GE Power Management
MM2 Motor Manager 2
6-15
6 COMMUNICATIONS
6.4 APPLICATIONS
6
6.4.2 STORING COMM ADDRESS USING THE BROADCAST COMMAND
The default setting for the communications address from the factory and after a 'Setpoint Dump' is
OFF. The communication speed and parity default settings are 9600 baud, no parity. We have pro-
vided a facility to store the comms. address to any MM2 without using the keypad and display (typi-
cally chassis mount MM2s).
Make sure the master is transmitting to the MM2 at 9600 baud, no parity. After installing the MM2
and ensuring communications is hooked up, cycle control voltage to the MM2 you wish to set the
address for. This will allow you to send a broadcast command with the new comms. address for the
MM2. The address must be set within 2 minutes of cycling power. Once the new address is stored or
the 2 minutes have elapsed, the MM2 will ignore all further attempts at changing the comms.
address unless power is cycled again. The address is changed using a broadcast command to
comms. address 0 and a command function code. Note: This procedure can be accomplished using
the MM2PC
®
software. See Chapter 8: MM2PC® SOFTWARE for details.
For example, to store communications address 25 to a new MM2 without a display, we have the fol-
lowing master/slave packet format. The master/slave packets have the following format:
Table 6–10: MASTER/SLAVE PACKET FORMAT (BROADCAST)
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
00
broadcast command for all units
FUNCTION CODE
1
10
store setpoints
DATA STARTING ADDRESS
2
11 60
setpoints address 1160
NUMBER OF SETPOINTS
2
00 03
3 setpoints = 6 bytes total
BYTE COUNT
1
06
6 bytes of data
DATA 1
2
00 05
data for address 1160
DATA 2
2
00 10
data for address 1161
DATA 3
2
00 19
data for address 1162
CRC
2
0B 8C
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
00
message from slave responding
FUNCTION CODE
1
10
store setpoints
DATA STARTING ADDRESS
2
11 60
setpoint address 1160
NUMBER OF SETPOINTS
2
00 03
3 setpoints
CRC
2
84 FB
CRC error code
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...