6.2.5 FUNCTION CODE 06H
Modbus Implementation: Preset Single Register
MM2 Implementation: Store Single Setpoint
This command allows the master to store a single setpoint into the memory of a MM2. The slave
response to this function code is to echo the entire master transmission.
For example, request slave 17 to store the value 01F4 in setpoint address 1020. After the transmis-
sion in this example is complete, setpoints address 1020 will contain the value 01F4. The master/
slave packet format is shown below:
Table 6–5: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 06H
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
06
store single setpoint
DATA STARTING ADDRESS
2
10 20
setpoint address 1020
DATA
2
01 F4
data for setpoint address 1020
CRC
2
8E 47
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave 17
FUNCTION CODE
1
06
store single setpoint
DATA STARTING ADDRESS
2
10 20
setpoint address 1020
DATA
2
01 F4
data stored in setpoint address 1020
CRC
2
8E 47
CRC error code
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...