GE Power Management
MM2 Motor Manager 2
5-3
5 ACTUAL VALUES
5.2 A1 DATA
5
5.2 A1 DATA
5.2.1 DESCRIPTION
This page contains the real-time data as measured by the MM2. Actual Values Page 1 is divided into
three sections, MOTOR DATA, PROCESS DATA, and PROGRAMMABLE MESSAGE.
5.2.2 MOTOR DATA
PATH: ACTUAL VALUES
t
A1: DATA
t
MOTOR DATA
MOTOR
STATUS:
This message indicates the name and status of the motor. The top line
of the display (20 characters) can be programmed to a user defined
alphanumeric name. The second line indicates motor status. The fol-
lowing list shows the possible motor status indications:
•
Unavailable: There is at least one condition present that is prevent-
ing start commands from operating. Possible conditions are: a trip is
present, the STOP key is being pressed, the Stop Switch input is
open, one of the Process Interlock switches is open, an undervolt-
age delayed restart is in progress, an Autotransformer Start Inhibit
is in progress, or the
STARTER TYPE
setpoint is
OFF
.
•
Available-Auto: Start commands from the serial port or the Auto
Start A / Auto Start B interlock switch inputs will be performed. Start
commands from the Start A / Start B switch inputs and the START
A/ START B keys will be ignored.
•
Available-Manual: Start commands from the Start A / Start B switch
inputs and/or the START A/ START B keys will be performed. Start
commands from the serial port and Auto Start A / Auto Start B
switch inputs will be ignored.
•
Running: At least one contactor output relay is closed.
A= 74
B= 74
C= 74
AMPS
This message displays the actual RMS current in each phase in amps.
Format: 10.0 at CT Primary
≤
50 A; 100 at CT Primary
>
50 A.
GROUND CURRENT =
2.4 AMPS
This message displays the ground fault leakage current flowing from
any phase to ground in amps.
MOTOR LOAD =
74% FULL LOAD
This message displays the motor load as a percentage of full load cur-
rent (FLC). The motor load is calculated as the average of the three
motor phase currents. When the value exceeds 100%, an overload con-
dition exists. The MM2 eventually trips if the current is not reduced
below 100% of FLC
×
SERVICE FACTOR.
GROUND CURRENT =
2.4 AMPS
This message displays the ground fault leakage current flowing from
any phase to ground in amps.
MOTOR LOAD =
74% FULL LOAD
This message displays the motor load as a percentage of full load cur-
rent (FLC). The motor load is calculated as the average of the three
motor phase currents. When the value exceeds 100%, an overload con-
dition exists. The MM2 eventually trips if the current is not reduced
below 100% of FLC
×
SERVICE FACTOR.
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...