GE Power Management
MM2 Motor Manager 2
6-33
6 COMMUNICATIONS
6.5 MEMORY MAP
6
ANALOG
INPUT
continued
44371
4370 1112 Analog High Override Delay
1-126
1
s
F1*
5
44372
4371 1113 ...Reserved...
...
...
...
...
...
44373
4372 1114 ...Reserved...
...
...
...
...
...
44374
4373 1115 ...Reserved...
...
...
...
...
...
44375
4374 1116 ...Reserved...
...
...
...
...
...
44376
4375 1117 ...Reserved...
...
...
...
...
...
44377
4376 1118 ...Reserved...
...
...
...
...
...
44378
4377 1119 ...Reserved...
...
...
...
...
...
44379
4378 111A ...Reserved...
...
...
...
...
...
44380
4379 111B ...Reserved...
...
...
...
...
...
44381
4380 111C ...Reserved...
...
...
...
...
...
44382
4381 111D ...Reserved...
...
...
...
...
...
44383
4382 111E ...Reserved...
...
...
...
...
...
44384
4383 111F ...Reserved...
...
...
...
...
...
U / V
AUTO
RESTART
44385
4384 1120 Undervoltage Restart
0-1
1
---
F14
1 = ENABLE
44386
4385 1121 Immediate Restart Power Loss Time 100-520
20
ms
F1*
200
44387
4386 1122 Delayed Restart Power Loss Time
1-101
1
0.1 x s F1***
20 = 2.0 s
44388
4387 1123 Restart Time Delay
2-12000
2
0.1 x s
F1
20 = 2.0 s
44389
4388 1124 ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44392
4391 1127 ...Reserved...
...
...
...
...
...
AUX 1
RELAY
44393
4392 1128 AUX Relay 1 Function
0-33
1
---
F20
0=SERIAL
CNTL
44394
4393 1129 AUX Relay 1 Delay
0-125
1
s
F1
5
44395
4394 112A AUX Relay 1 Motor Start Delay
0-125
1
s
F1
5
44396
4395 112B AUX Relay 1 Motor Stop Delay
0-125
1
s
F1
5
44397
4396 112C AUX Relay 1 Pre Delay
0-900
1
s
F1
5
44398
4397 112D AUX Relay 1 Post Delay
0-126
1
s
F1*
126 = OFF
44399
4398 112E AUX Relay 1 Operation
0-1
1
---
F12
0=non-failsafe
44400
4399 112F ...Reserved...
...
...
...
...
...
PLANT
CONDI-
TION
44401
4400 1130 Drive Greasing Interval
100-50100
100
hours
F1*
65535 = OFF
44402
4401 1131 Contactor Inspection Interval
1-10001
1
x1000 Op F1*
65535 = OFF
44403
4402 1132 Maximum Drive Stopped Time
100-10100
100
hours
F1*
65535 = OFF
44404
4403 1133 ...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
Table 6–12: MODBUS MEMORY MAP (Sheet 14 of 21)
GROUP
MOD-
ICON
REGISTER
ADDRESS
DESCRIPTION
REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC
HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...