GE Power Management
MM2 Motor Manager 2
4-19
4 SETPOINTS
4.3 S2 PROTECTION
4
4.3.8 UNDER/OVERVOLTAGE PROTECTION
PATH: SETPOINTS
tt
S2: PROTECTION
ttttt
UNDER/OVERVOLTAGE PROTECTION
UNDERVOLTAGE ALARM
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. This feature functions
the same as the Undervoltage Trip feature but produces an alarm indi-
cation instead of a trip.
UNDERVOLTAGE ALARM
DELAY: 10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Enter the delay for acti-
vation of the Undervoltage Alarm.
UNDERVOLTAGE TRIP
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. If the voltage remains
below this value while the motor is running for the time specified in the
UNDERVOLTAGE TRIP DELAY
, the MM2 will trip. Set this value to
OFF
if no
Undervoltage Trip is required.
UNDERVOLTAGE TRIP
DELAY: 10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Set the
UNDERVOLTAGE
TRIP DELAY
long enough to prevent nuisance trips from momentary volt-
age dips when the Undervoltage Trip feature is used.
OVERVOLTAGE ALARM
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. This feature functions
the same as the Overvoltage Trip feature but produces an alarm indica-
tion instead of a trip.
OVERVOLTAGE ALARM
DELAY:
10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Enter the delay for acti-
vation of the Overvoltage Alarm.
OVERVOLTAGE TRIP
LEVEL:
OFF V
Range: 0 to 600 V or OFF; Step: 1 V
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. If the voltage remains
above this value while the motor is running for the time specified in the
OVERVOLTAGE TRIP DELAY
, the MM2 will trip. Set this value to
OFF
if no
Overvoltage Trip is required.
OVERVOLTAGE TRIP
DELAY:
10 s
Range: 1 to 60 seconds; Step: 1 second
Appears if
VT PRIMARY VOLTAGE
is not set to
OFF
. Set the
OVERVOLTAGE
TRIP DELAY
long enough to prevent nuisance trips from momentary volt-
age dips when the Undervoltage Trip feature is used.
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...