GE Power Management
MM2 Motor Manager 2
5-7
5 ACTUAL VALUES
5.3 A2 STATUS
5
CONTACT INSPECTION
INTERVAL EXCEEDED
The number of contactor operations has exceeded the Contactor
Inspection Interval Alarm count.
MAXIMUM MOTOR
STOP TIME EXCEEDED
The time that the motor has remained stopped has exceeded the Maxi-
mum Motor Stopped Time alarm level. This can be cleared by starting
the motor.
ANALOG HIGH
ALARM
The Analog Input value has exceeded the Analog Input High Alarm
Level for the Analog Input High Alarm Time Delay.
ANALOG LOW
ALARM
The Analog Input value has dropped below the Analog Input Low Alarm
Level for the Analog Input Low Alarm Time Delay.
PROCESS INTERLOCK A
ALARM
An open Process Interlock A switch input has been detected.
PROCESS INTERLOCK B
ALARM
An open Process Interlock B switch input has been detected.
PROCESS INTERLOCK C
ALARM
An open Process Interlock C switch input has been detected.
PROCESS INTERLOCK D
ALARM
An open Process Interlock D switch input has been detected.
PROCESS INTERLOCK E
ALARM
An open Process Interlock E switch input has been detected.
PROCESS INTERLOCK F
ALARM
An open Process Interlock F switch input has been detected.
PROCESS INTERLOCK G
ALARM
An open Process Interlock G switch input has been detected.
PROCESS INTERLOCK H
ALARM
An open Process Interlock H switch input has been detected.
PROCESS INTERLOCK I
ALARM
An open Process Interlock I switch input has been detected.
PROCESS INTERLOCK J
ALARM
An open Process Interlock J switch input has been detected.
MOTOR A TRIP ALARM =
OVERLOAD
A Duty/Standby starter type motor has tripped. The cause of the trip is
displayed on the bottom line.
THERMAL CAPACITY
ALARM
The thermal capacity used has exceeded the Alarm level.
UNDERVOLTAGE
ALARM
The primary voltage measurement has dropped below the Alarm level.
OVERVOLTAGE
ALARM
The primary voltage measurement has exceeded the Alarm level.
START BLOCK
ALARM
A Start Block is in effect.
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...