GE Power Management
MM2 Motor Manager 2
4-29
4 SETPOINTS
4.5 S4 CONTROL
4
4.5.3 AUX RELAY 1/2 CONFIG
PATH: SETPOINTS
tttt
S4 CONTROL
tt
AUX 1/2 RELAY CONFIG
The MM2 has two auxiliary programmable output relays. These two outputs can be assigned any of
the functions listed below. Once a function has been assigned to one of the auxiliary relays it cannot
be assigned to the other with the exception of the SERIAL CONTROL function which can be set to
both auxiliary relays.
The setpoints listed under the
AUX RELAY 2 CONFIG
page operate in the same manner as
the setpoints shown for
AUX RELAY 1 CONFIG
.
AUX RELAY 1 FUNCTION:
SERIAL CONTROL
Range: SERIAL CONTROL, TRIPS, ALARMS, PRE CONTACTOR A,
POST CONTACTOR A, POST CONTACTOR B, MOTOR AVAILABLE-
MAN, LOAD INCREASE ALARM, UNDERCURRENT TRIP, UNDER-
POWER TRIP, KEYPAD RESET, INTERLOCK 1 to INTERLOCK 10,
AUTO MODE, MOTOR RUNNING, GROUND FAULT TRIP, WYE-
DELTA CLS TRANS, AUTOTRANSFORMER 2S, NOT USED, PRE
CONTACTOR B, SEGREGATED G/F ALARM, THERMAL CAPACITY
ALARM, MOTOR AVAILABLE AUTO, MOTOR AVAILABLE, OVER-
LOAD, SOFT STARTER BYPASS
The dual form “C” AUX Relay 1 can be configured to activate on various
conditions as described below.
AUX RELAY 1 DELAY
5 s
Range: 0 to 125 sec.; Step: 1
Provides a delayed energization of AUX Relay 1 when
POST CONTACTOR
A
or
POST CONTACTOR B
is selected as the
AUX RELAY 1 FUNCTION
.
AUX RELAY 1 PRE
START DELAY: 5 s
Range: 0 to 900 sec.; Step: 1
Determines how long the AUX Relay 1 will energize before energizing
Contactor A. When set to
0
, both AUX Relay 1 and Contactor A will
energize at the same time.
AUX RELAY 1 POST
START DELAY: OFF s
Range: 0 to 125 sec. or OFF; Step: 1
Determines how long AUX 1 remains energized after Contactor A
closes. When set to
0
, AUX 1 de-energizes as soon as Contactor A
closes. When set to
OFF
, AUX 1 remains energized until Contactor A
opens.
ENERGIZE ON MOTOR
START DELAY: 5 s
Range: 0 to 125 sec.; Step: 1
Provides a delayed energization of the AUX Relay 1 when
MOTOR RUN-
NING
is selected as the
AUX RELAY 1 FUNCTION
. The AUX Relay 1 ener-
gizes after this time delay on the occurrence of a motor start.
DE-ENERGIZE ON MOTOR
STOP DELAY: 5 s
Range: 0 to 125 sec.; Step: 1
Provides a delayed de-energization of the AUX Relay 1 when
MOTOR
RUNNING
is selected as the
AUX RELAY 1 FUNCTION
. The AUX Relay 1 will
de-energize after this time delay on the occurrence of a motor stop.
NOTE
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...