MM2 Motor Manager 2
GE Power Management
A.1 COMMISIONING SUMMARY
APPENDIX A
A
Ground Fault Trip Level
Off
Gnd Fault Trip Delay On Run
1.0 sec.
Gnd Fault Trip Delay On Start
1.0 sec.
MOTOR PROTECTION – OPTIONS
Minimize Reset Time
Enable
Stopped Motor Cool Time
30 min.
Overload Trip Reset
Manual
Reset Lockout using Reset Key
Enable
Phase Unbalance Alarm
Enable
Thermal Capacity Alarm
Off
Open Control Circuit Trip
Enable
Reset Alarms Using Reset Key
Enable
LOAD PROTECTION
Underpower Alarm Level
Off
Underpower Alarm Delay
10 sec.
Underpower Trip Level
Off
Underpower Trip Delay
10 sec.
Acceleration Time Alarm
Off
Acceleration Time Trip
Off
Load Increase Alarm
Off
Undercurrent Alarm Level
Off
Undercurrent Alarm Delay
10 sec.
Undercurrent Trip Level
Off
Undercurrent Trip Delay
10 sec.
Stalled Rotor Trip Level
4.50 x FLC
Stalled Rotor Trip Delay
3.0 sec.
UNDER/OVERVOLTAGE PROTECTION
Undervoltage Alarm Level
Off
Undervoltage Alarm Delay
10 sec.
Undervoltage Trip Level
Off
Undervoltage Trip Delay
10 sec.
Overvoltage Alarm Level
Off
Overvoltage Alarm Delay
10 sec.
Table A–1: MM2 COMMISSIONING (Sheet 3 of 8)
DESCRIPTION
DEFAULT
VALUE
Overvoltage Trip Level
Off
Overvoltage Trip Delay
10 sec.
S3: PROCESS
PROGRAMMABLE INPUTS
Interlock Input 1
Not Used
Startup Override Delay 1
0 sec.
Running Override Delay 1
0 sec.
Operation 1
Stop
Instantaneous Alarm 1
Disable
IL1 Switch Type
N.O.
Interlock Input 2
Not Used
Startup Override Delay 2
0 sec.
Running Override Delay 2
0 sec.
Operation 2
Stop
Instantaneous Alarm 2
Disable
IL2 Switch Type
N.O.
Interlock Input 3
Not Used
Startup Override Delay 3
0 sec.
Running Override Delay 3
0 sec.
Operation 3
Stop
Instantaneous Alarm 3
Disable
IL3 Switch Type
N.O.
Interlock Input 4
Not Used
Startup Override Delay 4
0 sec.
Running Override Delay 4
0 sec.
Operation 4
Stop
Instantaneous Alarm 4
Disable
IL4 Switch Type
N.O.
Interlock Input 5
Not Used
Startup Override Delay 5
0 sec.
Running Override Delay 5
0 sec.
Operation 5
Stop
Instantaneous Alarm 5
Disable
Table A–1: MM2 COMMISSIONING (Sheet 4 of 8)
DESCRIPTION
DEFAULT
VALUE
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...