GE Power Management
MM2 Motor Manager 2
6-17
6 COMMUNICATIONS
6.4 APPLICATIONS
6
6.4.4 USER DEFINABLE MEMORY MAP DEFAULT VALUES
For convenience default User Map values have been added. However, the User Definable Memory
Map is still fully customizable. The defaults are separated into three sections. Regular Polling data
items, data that is read when a Trip, Stop or Alarm occurs, and data that can be monitored as time
permits.
Table 6–11: MM2 MEMORY MAP USER DEFINABLE OUTPUTS (Sheet 1 of 2)
MODICON
REGULAR
ADDRESS
DESCRIPTION
REGISTER
VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FORMAT
USER MAP
DEFAULT
ADDRESS
(HEX)
DEC
HEX
30021
20
0014
Gen Alarm Active Status Flags 1
F104
100
30022
21
0015
Gen Alarm Active Status Flags 2
F105
101
30023
22
0016
Interlock Alarm Active Status Flags
F106
102
30027
26
001A
Interlock Start Block Status Flags
F106
103
30028
27
001B
Trip Active Status Flags 1
F107
104
30029
28
001C
Trip Active Status Flags 2
F108
105
30035
34
0022
Command Mode
F6
106
30036
35
0023
Drive Status
F7
107
30037
36
0024
Motor Mode
F8
108
30049
48
0030
Phase Current Scale Factor
F1
109
30050
49
0031
Phase A Current
F1
10A
30051
50
0032
Phase B Current
F1
10B
30052
51
0033
Phase C Current
F1
10C
30053
52
0034
Ground Current
F1
10D
30054
53
0035
Motor Load
%FLC
F1
10E
30055
54
0036
Thermal Capacity
%
F1
10F
30056
55
0037
Current Unbalance
%
F1
110
30017
16
0010
Switch Input Status
F100
111
30020
19
0013
Operation Status Flags
F103
112
30034
33
0021
Cause of Stop
F5
113
30057
56
0038
Acceleration Time
0.1 x s
F1
114
30058
57
0039
Last Starting Current
F1
115
30059
58
003A
O/L Time to Trip
F1
116
30081
80
0050
Cause of Trip
F9
117
30082
81
0051
Time to Reset
min.
F1
118
30083
82
0052
Pre Trip Phase A Current
F1
119
30084
83
0053
Pre Trip Phase B Current
F1
11A
Shading codes:
Regular Polling
Upon a Trip, Alarm, Stop
Monitor as time permits
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...