6.2 MODBUS FUNCTIONS
6 COMMUNICATIONS
6
6.2.2 FUNCTION CODE 03H
Modbus implementation: Read Holding Registers
MM2 implementation: Read Setpoints and Actual Values
For the MM2 implementation of Modbus, this command can be used to read any setpoints ("holding
registers") or actual values ("input registers"). Holding and input registers are 16 bit (two byte) values
transmitted high order byte first. Thus all MM2 Setpoints and Actual Values are sent as two bytes.
The maximum number of registers that can be read in one transmission is 125. This function code is
identical to function code 04.
The slave response to this function code is the slave address, function code, a count of the number
of data bytes to follow, the data itself and the CRC. Each data item is sent as a two byte number with
the high order byte sent first.
For example, consider a request for slave 17 to respond with 3 registers starting at address 006B.
For this example the register data in these addresses is as follows:
The master/slave packets have the following format:
Address
Data
006B
022B
006C
0000
006D
0064
Table 6–2: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 03H
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
03
read registers
DATA STARTING ADDRESS
2
00 6B
data starting at 006B
NUMBER OF SETPOINTS
2
00 03
3 registers = 6 bytes total
CRC
2
76 87
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave 17
FUNCTION CODE
1
03
read registers
BYTE COUNT
1
06
3 registers = 6 bytes
DATA 1 (see definition above)
2
02 2B
value in address 006B
DATA 2 (see definition above)
2
00 00
value in address 006C
DATA 3 (see definition above)
2
00 64
value in address 006D
CRC
2
54 83
CRC error code
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...