6-8
MM2 Motor Manager 2
GE Power Management
6.2 MODBUS FUNCTIONS
6 COMMUNICATIONS
6
6.2.4 FUNCTION CODE 05H
Modbus Implementation: Force Single Coil
MM2 Implementation: Execute Operation
This function code allows the master to request a MM2 to perform specific command operations. The
commands supported by the MM2 are listed in Section 6.4: APPLICATIONS on page 6–14.
For example, to request slave 17 to execute operation code 1 (reset), we have the following master/
slave packet format:
The commands that can be performed by the MM2 using function code 05 can also be initiated by
using function code 10.
See Section 6.2.8: FUNCTION CODE 10H on page 6–12 for an example of performing commands
using function code 10.
Table 6–4: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 05H
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
05
execute operation
OPERATION CODE
2
00 01
operation code 1
CODE VALUE
2
FF 00
perform function
CRC
2
DF 6A
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave 17
FUNCTION CODE
1
05
execute operation
OPERATION CODE
2
00 01
operation code 1
CODE VALUE
2
FF 00
perform function
CRC
2
DF 6A
CRC error code
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...