GE Power Management
MM2 Motor Manager 2
6-5
6 COMMUNICATIONS
6.2 MODBUS FUNCTIONS
6
6.2 MODBUS FUNCTIONS
6.2.1 FUNCTION CODE 01H
Modbus implementation: Read Coil Status
MM2 implementation: Read Last Command Operation
This function code allows the master to read back which command operation was last performed
using Modbus function code 05: force single coil/execute operation. Upon request of coil/operation
status, the MM2 will set a bit corresponding to the last operation performed. The operation com-
mands are in the Modbus Data Formats table under code F22.
Note: Operation 0 will be set (1) if no operations have been performed since the MM2 has been pow-
ered up.
For example, a request slave 17 to respond with status of 6 operations, starting at operation 10, after
performing command operation 13 (Manual Inhibit) has the following format:
The DATA 1 definition is as follows:
Table 6–1: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 01H
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
01
read last command operation
OPERATION STARTING ADDRESS
2
00 0A
start at operation 10
NUMBER OF OPERATIONS TO READ
2
00 06
read 6 operations
CRC
2
9E 9A
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave 17
FUNCTION CODE
1
01
read last command operation
BYTE COUNT
1
01
6 operations = 6 bits: only 1 byte required
DATA 1 (see definition below)
1
08
bit set corresponding to command 13
CRC
2
54 83
CRC error code
Data 1 = 08 (hex) =
0
0
0
0
1
0
0
0
command operation #
N/A
N/A
15
14
13
12
11
10
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...