1-6
MM2 Motor Manager 2
GE Power Management
1.3 SPECIFICATIONS
1 INTRODUCTION
1
MM2 CONTACTOR A & B AND AUX 2 OUTPUT RELAY CONTACTS
CONFIGURATION:
CONTACTOR A AND B: Form A
AUX RELAY 2: Form C
CONTACT MATERIAL:
Silver Alloy (AgCdO)
MAX. OPERATING VOLTAGE: 280 V AC, 250 V DC
MAXIMUM PERMISSIBLE LOAD: 5 V DC, 100 mA
MM2 AUX 1 OUTPUT RELAY CONTACTS
CONFIGURATION:
Dual Form C
CONTACT MATERIAL:
Silver Alloy (AgCdO)
MAX. OPERATING VOLTAGE: 280 V AC, 125 V DC
UNDERVOLTAGE – SUPPLY VOLTAGE
UNDERVOLTAGE:
65% of nominal (120 V AC or 240 V AC);
Immediate restart for maximum dip time of 0.1 to 0.5 seconds or OFF;
Delayed restart for maximum dip time of 0.1 to 10.0 seconds or UNLIMITED time
DELAY RESTART RANGE: 0.2 to 300 seconds
DELAY RESTART ACCURACY: ±0.2 seconds
VOLTAGE
BREAK
MAKE/CARRY
CONTINUOUS
MAKE/CARRY
0.2 seconds
RESISTIVE
30 V DC
10 A
10 A
30 A
125 V DC
0.5 A
250 V DC
0.3 A
INDUCTIVE
(L/R = 7 ms)
30 V DC
5 A
125 V DC
0.25 A
250 V DC
0.15 A
RESISTIVE
120 V AC
10 A
240 V AC
INDUCTIVE
(PF = 0.4)
120 V AC
10 A
225 V AC
8 A
VOLTAGE
BREAK
MAKE/CARRY
CONTINUOUS
MAKE/CARRY
0.2 seconds
RESISTIVE
30 V DC
5 A
5 A
15 A
125 V DC
0.25 A
INDUCTIVE
(L/R = 7 ms)
30 V DC
2.5 A
125 V DC
0.1 A
RESISTIVE
120 V AC
5 A
240 V AC
INDUCTIVE
(PF = 0.4)
120 V AC
5 A
225 V AC
3 A
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...