9-28
MM2 Motor Manager 2
GE Power Management
9.9 PART WINDING STARTER
9 STARTER TYPES
9
9.9 PART WINDING STARTER
9.9.1 DESCRIPTION
The functionality of this starter is currently under review.
To program the MM2 for part winding starter, set:
1.
S1 CONFIGURATION\STARTER\STARTER TYPE:
PART WINDING
S1 CONFIGURATION\STARTER\STAGE ONE SHORTING TIME:
1 to 125 sec.
The
STAGE ONE SHORTING TIME
setpoint appears when the
STARTER TYPE
is selected as
PART WINDING
.
This is the time delay from the closure of Contactor A until the closure of Contactor B.
9.9.2 MM2 SEQUENCE
START sequence:
1. Start command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Contactor A output relay.
3. Wait for the time set in the
STAGE ONE SHORTING TIME DELAY
setpoint.
4. Close and maintain Contactor B output relay.
STOP/TRIP sequence:
1. Stop command is received by the MM2 or a trip occurs.
2. Open contactors A and B output relays.
If feedback is not received from the Contactor A and B Status N.O. inputs within one second of clos-
ing Contactor A and B output relays, an OPEN CONTROL CIRCUIT alarm will occur. This will cause
Contactor A and B output relays to open.
If feedback remains at Contactor A or B Status N.O. input more than one second after opening the
Contactor A or B output relays, a WELDED CONTACTOR alarm will occur.
NOTE
Summary of Contents for MOTOR MANAGER 2
Page 2: ......
Page 4: ......
Page 34: ...3 8 MM2 Motor Manager 2 GE Power Management 3 3 THEORY OF OPERATION 3 HARDWARE 3 ...
Page 80: ...5 12 MM2 Motor Manager 2 GE Power Management 5 5 A4 STATISTICS 5 ACTUAL VALUES 5 ...
Page 188: ...9 40 MM2 Motor Manager 2 GE Power Management 9 13 SOFT STARTER 9 STARTER TYPES 9 ...
Page 212: ...E 4 MM2 Motor Manager 2 GE Power Management E 1 CT ISOLATION APPENDIXE E ...
Page 220: ...iv MM2 Motor Manager 2 GE Power Management INDEX ...