GE Multilin
L30 Line Current Differential System
B-87
APPENDIX B
B.4 MEMORY MAPPING
B
F530
ENUMERATION: FRONT PANEL INTERFACE KEYPRESS
F531
ENUMERATION: LANGUAGE
0 = English, 1 = French, 2 = Chinese, 3 = Russian, 4 = Turkish
F540
ENUMERATION: PMU POST-FILTER
0 = None, 1 = Symm-3-Point, 2 = Symm-5-Point,
3 = Symm-7-Point, 4 = Class M, 5 = Class P
F542
ENUMERATION: PMU TRIGGERING MODE
0 = Automatic Overwrite, 1 = Protected
F543
ENUMERATION: PMU PHASORS
F544
ENUMERATION: PMU RECORDING/REPORTING RATE
F545
ENUMERATION: PMU COM PORT TYPE
0 = Network, 1 = RS485, 2 = Dir Comm Ch1, 3 = Dir Comm Ch2,
4 = GOOSE, 5 = None
F546
ENUMERATION: PMU REPORTING STYLE
0 = Polar, 1 = Rectangular
F547
ENUMERATION: PMU REPORTING FORMAT
0 = Integer, 1 = Floating
F560
ENUMERATION: IN-ZONE TRANSFORMER CONNECTION
F561
ENUMERATION: 87L INRUSH INHIBIT MODE
value
keypress
value
keypress
value
keypress
0
None
15
3
33
User PB 3
1
Menu
16
Enter
34
User PB 4
2
Message Up
17
Message
Down
35
User PB 5
3
7
~
18
0
~
36
User PB 6
4
8
19
Decimal
37
User PB 7
5
9
20
+/–
38
User PB 8
6
Help
21
Value Up
39
User PB 9
7
Message Left
22
Value Down
40
User PB 10
8
4
23
Reset
41
User PB 11
9
5
24
User 1
42
User PB 12
10
6
25
User 2
44
User 4
11
Escape
26
User 3
45
User 5
12
Message
Right
31
User PB 1
46
User 6
13
1
32
User PB 2
47
User 7
14
2
value
phasor
value
phasor
0
Off
8
Ig
1
Va
9
V_1
2
Vb
10
V_2
3
Vc
11
V_0
4
Vx
12
I_1
5
Ia
13
I_2
6
Ib
14
I_0
7
Ic
value
rate
value
rate
0
1/second
7
20second
1
2/second
8
25/second
2
4/second
9
30/second
3
5/second
10
50/second
4
10/second
11
60/second
5
12/second
12
100/second
6
15/second
13
120/second
Enumeration
In-zone transformer connnection
0
None
1
0° lag
2
30° lag
3
60° lag
4
90° lag
5
120° lag
6
150° lag
7
180° lag
8
210° lag
9
240° lag
10
270° lag
11
300° lag
12
330° lag
Enumeration
Inrush inhibit mode
0
Disabled
1
Per phase
2
Two out of three
3
Average
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...