5-40
L30 Line Current Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The GGIO5 integer configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO5 ANALOG CONFIGURATION
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the L30. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
•
GGIO5 UINT IN 1 VALUE
: This setting selects the FlexInteger value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
REPORT CONTROL CONFIGURATION
CONFIGURABLE REPORT 1
REPORT 1 DATASET ITEMS
To create the dataset for logical node LN, program the
ITEM 1
to
ITEM 64
settings to a value from the list of IEC 61850 data
attributes supported by the L30. Changes to the dataset will only take effect when the L30 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
GGIO5 UINTEGER
CONFIGURATION
GGIO5 UINT In 1:
Off
Range: Off, any FlexInteger
™
parameter
MESSAGE
GGIO5 UINT In 2:
Off
Range: Off, any FlexInteger parameter
MESSAGE
GGIO5 UINT In 3:
Off
Range: Off, any FlexInteger parameter
MESSAGE
GGIO5 UINT 1n 16:
Off
Range: Off, any FlexInteger parameter
REPORT 1
DATASET ITEMS
ITEM 1:
Range: all valid MMS data item references
MESSAGE
ITEM 2:
Range: as shown above
MESSAGE
ITEM 3:
Range: as shown above
MESSAGE
ITEM 64:
Range: as shown above
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...