GE Multilin
L30 Line Current Differential System
5-49
5 SETTINGS
5.2 PRODUCT SETUP
5
c) LOCAL TIME
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
LOCAL TIME
The
LOCAL TIME OFFSET FROM UTC
setting is used to specify the local time zone offset from Universal Coordinated Time
(Greenwich Mean Time) in hours. Time zones in the eastern hemisphere have positive values; time zones in the western
hemisphere have negative values. A value of zero causes the relay to use UTC for local time. This setting has two uses.
When the system RTC is synchronized with IRIG-B or is free-running, the offset setting is used to calculate UTC time from
the local time these provide. When the RTC is synchronized with PTP or SNTP, the offset is used to determine local time
from the UTC time provided by PTP or SNTP. PTP ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used in calcu-
lating local time.
The
DAYLIGHT SAVINGS TIME (DST)
settings can be used to allow the relay to follow the DST rules of the local time zone.
Note that when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time
offset and so the DST settings are ignored.
LOCAL TIME
LOCAL TIME OFFSET
FROM UTC:
0.0 hrs
Range: –24.0 to 24.0 hrs in steps of 0.5
MESSAGE
DAYLIGHT SAVINGS
TIME: Disabled
Range: Disabled, Enabled
MESSAGE
DST START MONTH:
January
Range: January to December (all months)
MESSAGE
DST START DAY:
Sunday
Range: Sunday to Saturday (all days of the week)
MESSAGE
DST START DAY
INSTANCE: First
Range: First, Second, Third, Fourth, Last
MESSAGE
DST START HOUR:
2:00
Range: 0:00 to 23:00
MESSAGE
DST STOP MONTH:
January
Range: January to December (all months)
MESSAGE
DST STOP DAY:
Sunday
Range: Sunday to Saturday (all days of the week)
MESSAGE
DST STOP DAY
INSTANCE: First
Range: First, Second, Third, Fourth, Last
MESSAGE
DST STOP HOUR:
2:00
Range: 0:00 to 23:00
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...