B-72
L30 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F117
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 1
72 cycles, 1 = 3
36 cycles, 2 = 7
18 cycles, 3 = 15
9 cycles
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
F119
ENUMERATION: FLEXCURVE PICKUP RATIOS
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
F124
ENUMERATION: LIST OF ELEMENTS
mask
value
mask
value
mask
value
mask
value
0
0.00
30
0.88
60
2.90
90
5.90
1
0.05
31
0.90
61
3.00
91
6.00
2
0.10
32
0.91
62
3.10
92
6.50
3
0.15
33
0.92
63
3.20
93
7.00
4
0.20
34
0.93
64
3.30
94
7.50
5
0.25
35
0.94
65
3.40
95
8.00
6
0.30
36
0.95
66
3.50
96
8.50
7
0.35
37
0.96
67
3.60
97
9.00
8
0.40
38
0.97
68
3.70
98
9.50
9
0.45
39
0.98
69
3.80
99
10.00
10
0.48
40
1.03
70
3.90
100
10.50
11
0.50
41
1.05
71
4.00
101
11.00
12
0.52
42
1.10
72
4.10
102
11.50
13
0.54
43
1.20
73
4.20
103
12.00
14
0.56
44
1.30
74
4.30
104
12.50
15
0.58
45
1.40
75
4.40
105
13.00
16
0.60
46
1.50
76
4.50
106
13.50
17
0.62
47
1.60
77
4.60
107
14.00
18
0.64
48
1.70
78
4.70
108
14.50
19
0.66
49
1.80
79
4.80
109
15.00
20
0.68
50
1.90
80
4.90
110
15.50
21
0.70
51
2.00
81
5.00
111
16.00
22
0.72
52
2.10
82
5.10
112
16.50
23
0.74
53
2.20
83
5.20
113
17.00
24
0.76
54
2.30
84
5.30
114
17.50
25
0.78
55
2.40
85
5.40
115
18.00
26
0.80
56
2.50
86
5.50
116
18.50
27
0.82
57
2.60
87
5.60
117
19.00
28
0.84
58
2.70
88
5.70
118
19.50
29
0.86
59
2.80
89
5.80
119
20.00
bitmask
element
0
Phase Instantaneous Overcurrent 1
1
Phase Instantaneous Overcurrent 2
2
Phase Instantaneous Overcurrent 3
3
Phase Instantaneous Overcurrent 4
4
Phase Instantaneous Overcurrent 5
5
Phase Instantaneous Overcurrent 6
6
Phase Instantaneous Overcurrent 7
7
Phase Instantaneous Overcurrent 8
16
Phase Time Overcurrent 1
17
Phase Time Overcurrent 2
18
Phase Time Overcurrent 3
19
Phase Time Overcurrent 4
24
Phase Directional Overcurrent 1
25
Phase Directional Overcurrent 2
32
Neutral Instantaneous Overcurrent 1
33
Neutral Instantaneous Overcurrent 2
34
Neutral Instantaneous Overcurrent 3
35
Neutral Instantaneous Overcurrent 4
36
Neutral Instantaneous Overcurrent 5
37
Neutral Instantaneous Overcurrent 6
38
Neutral Instantaneous Overcurrent 7
39
Neutral Instantaneous Overcurrent 8
48
Neutral Time Overcurrent 1
49
Neutral Time Overcurrent 2
50
Neutral Time Overcurrent 3
51
Neutral Time Overcurrent 4
56
Neutral Directional Overcurrent 1
57
Neutral Directional Overcurrent 2
64
Ground Instantaneous Overcurrent 1
65
Ground Instantaneous Overcurrent 2
66
Ground Instantaneous Overcurrent 3
67
Ground Instantaneous Overcurrent 4
68
Ground Instantaneous Overcurrent 5
69
Ground Instantaneous Overcurrent 6
70
Ground Instantaneous Overcurrent 7
71
Ground Instantaneous Overcurrent 8
80
Ground Time Overcurrent 1
81
Ground Time Overcurrent 2
82
Ground Time Overcurrent 3
83
Ground Time Overcurrent 4
96
Negative Sequence Instantaneous Overcurrent 1
97
Negative Sequence Instantaneous Overcurrent 2
112
Negative Sequence Time Overcurrent 1
113
Negative Sequence Time Overcurrent 2
120
Negative Sequence Overvoltage
140
Auxiliary Undervoltage 1
144
Phase Undervoltage 1
145
Phase Undervoltage 2
148
Auxiliary Overvoltage 1
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...