F
Diagnostics and fault clearance
394
Festo – EMCA-EC-C-HP-EN – 2017-11e – English
Diagnostic messages and fault clearance
25h
Path calculation
Definable as:
F
/-/-
Diagnostic memory: optional
The positioning target cannot be reached through the positioning options or the edge conditions.
During record sequencing: the end speed of the last record was higher than the target speed of the
following record.
Check the parameterisation of the affected records.
Also check the actual values of the previous positioning process at the switching point, if neces
sary, by using the trace function. The error may be caused by the actual velocity or the actual
acceleration being too high at the switching point. In case of parameterisation via fieldbus:
Speed and accelerationmust not equal 0.
–
Resettable: Error can be reset immediately.
Definable error response(s): A
26h
CAN fieldbus parameters missing
Definable as:
F
/-/-
Diagnostic memory: optional
Parameterisation for operation on the CAN bus is incomplete.
Complete the missing parameters and perform a software reset.
–
Resettable: Error can be reset immediately.
Definable error response(s):
B
, C, D, E, F, G
27h
Save parameters
Definable as:
F
/-/-
Diagnostic memory: optional
Error during writing of the internal permanent memory.
Execute the last operation again.
Check the following: Is an error present that can be reset first? When downloading a parameter
file, check if the version of the parameter file fits the firmware. If the error occurs again, please
contact Festo Service.
–
Resettable: Error can be reset immediately.
Definable error response(s):
F
, G
28h
Homing required
Definable as:
F
/W/-
Diagnostic memory: optional
A valid homing process has not yet been conducted.
The drive is no longer referenced (e.g. as a result of a logic power failure or because the homing
method or axis zero point has been changed).
Perform homing or repeat the last homing if it was not completed successfully.
–
If parameterised as an error: Error can be reset immediately.
Definable error response(s):
B
, C, D, E, F, G
–
For parameterisation as a warning: The warning disappears if the homing run has been completed
successfully.
Summary of Contents for EMCA-EC-67 CO Series
Page 33: ...2 CANopen Festo EMCA EC C HP EN 2017 11e English 33 ...
Page 73: ...3 EtherCAT with FHPP Festo EMCA EC C HP EN 2017 11e English 73 ...
Page 87: ...4 EtherNet IP with FHPP Festo EMCA EC C HP EN 2017 11e English 87 ...
Page 113: ...6 PROFINET IO with FHPP Festo EMCA EC C HP EN 2017 11e English 113 ...
Page 116: ...7 FHPP 116 Festo EMCA EC C HP EN 2017 11e English ...
Page 140: ...8 FHPP standard data I O data 140 Festo EMCA EC C HP EN 2017 11e English ...
Page 148: ...9 Measuring reference system 148 Festo EMCA EC C HP EN 2017 11e English ...
Page 210: ...10 Control via FHPP 210 Festo EMCA EC C HP EN 2017 11e English ...
Page 223: ...11 Monitoring of the drive behaviour Festo EMCA EC C HP EN 2017 11e English 223 ...
Page 367: ...D CANopen communication Festo EMCA EC C HP EN 2017 11e English 367 ...
Page 402: ...F Diagnostics and fault clearance 402 Festo EMCA EC C HP EN 2017 11e English ...
Page 413: ...EMCA EC 67 CO DIO EC EP PN Festo EMCA EC C HP EN 2017 11e English 413 ...
Page 414: ...EMCA EC 67 CO DIO EC EP PN 414 Festo EMCA EC C HP EN 2017 11e English ...
Page 415: ......