C
FHPP parameters (PNU)
266
Festo – EMCA-EC-C-HP-EN – 2017-11e – English
PNU 204
Diagnostic memory parameter (Diagnostics buffer parameter)
Subindex 3, 4
Class: Struct
Data type: uint8
Mappable
Access: ro, wo
Reading or deleting of the diagnostic memory.
Subindex 3
Clear diagnostic memory (Delete memory)
Access: wo
Clearing the diagnostic memory.
Value
Significance
1
Diagnostic memory is cleared
Subindex 4
Number of entries (Number of entries)
Access: ro
Read out the number of valid entries in the diagnostic memory
Value
Significance
0 … 200
No. of
Tab. C.32
PNU 204
PNU 205
Device fault (Device fault)
Subindex 1
Class: Var
Data type: uint16
Mappable
Access: ro
Read the active fault with the highest priority.
If no fault is present, 0xFFFF (65535) is returned.
Tab. C.33
PNU 205
Summary of Contents for EMCA-EC-67 CO Series
Page 33: ...2 CANopen Festo EMCA EC C HP EN 2017 11e English 33 ...
Page 73: ...3 EtherCAT with FHPP Festo EMCA EC C HP EN 2017 11e English 73 ...
Page 87: ...4 EtherNet IP with FHPP Festo EMCA EC C HP EN 2017 11e English 87 ...
Page 113: ...6 PROFINET IO with FHPP Festo EMCA EC C HP EN 2017 11e English 113 ...
Page 116: ...7 FHPP 116 Festo EMCA EC C HP EN 2017 11e English ...
Page 140: ...8 FHPP standard data I O data 140 Festo EMCA EC C HP EN 2017 11e English ...
Page 148: ...9 Measuring reference system 148 Festo EMCA EC C HP EN 2017 11e English ...
Page 210: ...10 Control via FHPP 210 Festo EMCA EC C HP EN 2017 11e English ...
Page 223: ...11 Monitoring of the drive behaviour Festo EMCA EC C HP EN 2017 11e English 223 ...
Page 367: ...D CANopen communication Festo EMCA EC C HP EN 2017 11e English 367 ...
Page 402: ...F Diagnostics and fault clearance 402 Festo EMCA EC C HP EN 2017 11e English ...
Page 413: ...EMCA EC 67 CO DIO EC EP PN Festo EMCA EC C HP EN 2017 11e English 413 ...
Page 414: ...EMCA EC 67 CO DIO EC EP PN 414 Festo EMCA EC C HP EN 2017 11e English ...
Page 415: ......