4. Commissioning
4-18
Festo P.BE-DLP-VSE-... en 0206a
Device data base correctly (see step 1 of the prepara-
tions).
3. Hold the left-hand mouse key pressed down and pull the
cursor onto the graphic PROFIBUS line on the DP master
(drag and drop)
3
.
4. The entry mask “Properties PROFIBUS node” will then
appear.
Select the slave (PROFIBUS) address identical to the se-
lected setting of the DIL switch in the switch module (see
chapter 3.3.2) and confirm with OK.
The icon of the Local control unit appears in the PROFI-
BUS line (see Fig. 4/6).
5. Mark the icon of the Local control unit
4
to be configured
on the graphic user level of the Hardware config. The con-
figuration data with the columns “DP ID”, “Order
number”, “Input address”, “Output address”, “Comment”
appear in the table in the lower half of the monitor screen.