3. Installation
3-19
Festo P.BE-DLP-VSE-... en 0206a
The maximum permitted length of a branch line depends on
the cable type and on the baud rate.
Baud rate
(in kBaud)
Field bus length
(max.)
Maximum per-
mitted branch
line length
9.6
1200 m
500 m
19.2
1200 m
500 m
93.75
1200 m
100 m
187.5
1000 m
33.3 m
500
400 m
20 m
1500
200 m
6.6 m
3000-12000
100 m
—
Fig. 3/23: Maximum permitted field bus and branch line
lengths for PROFIBUS-DP depending on the baud
rate
Recommendation:
Use a cable with a capacitance per unit length of < 30 nF/km
as specified below.
Otherwise the permitted cable length will have to be reduced.
Cable specification as per EN 50170 (cable type A):
Surge impedance
135-165 Ohm (3-20 MHz)
Capacitance per unit length < 30 nF/km
Loop impedance
< 110 Ohm/km
Core diameter
> 0.64 mm
Core cross sectional area
> 0.34 mm
2