A. Technical specifications and index
A-3
Festo P.BE-DLP-VSE-... en 0206a
PROFIBUS-DP
(only DLP-VSE-...-DP)
Field bus
RS 485, as per EN 50170
Inputs
– Number
– Minimum voltage
– Maximum voltage
– Log. “1”
– Log. “0”
– Current consumption
– Output current (sum of all
sensor supply outputs)
4
0 V
30 V
≥
10 V
≤
5 V
typ. 12 mA
max. 1 A (short-circuit resistant,
protected against incorrect po-
larity)
Outputs
– Number
– Current
– Voltage
4
max. 500 mA per output
max. 30 V
AS-Interface
(only DLP-VSE-...-ASI)
Bus connection
– Voltage range
– Residual ripple
26.5 V ... 31.6 V DC
protected against incorrect po-
larity
≤
20 mVpp
Load voltage connection
– Rated value
– Residual ripple
– Current consumption (at 24 V)
24 V DC ...
-15%/+20% (20.4 ... 28.8 V DC)
4 Vpp
140 mA
AS-Interface profile
ID code = F
H
; IO code = 7
H
S-7.F
Summary of Contents for DLP-VSE Series