3. Installation
3-13
Festo P.BE-DLP-VSE-... en 0206a
Proceed as follows:
1. Switch off the operating voltage.
2. Dismantle the switch module (see chapter 3.3.1)
3. Set the configuration of the Local control unit (4-element
DIL switch, element 1).
4. Assign an unused station number to the Local control
unit. Set the desired station number (8-element DIL
switch,
elements 1-7).
5. Set the diagnostic mode (8-element DIL switch,
element 8).
6. Fit the switch module (see chapter 3.3.1)
1
Configuration
with/without
measurement
bus
2
not assigned
3
Address selector
switch for station
number
4
Setting the diag-
nostic mode
1
2
3
4
O N
1
2
3
4
5
6
7
8
O N
1
2
3
4
Fig. 3/18: DIL switch in the switch module