3. Installation
3-28
Festo P.BE-DLP-VSE-... en 0206a
3.4.4 Connecting the AS-i bus and the load voltage
Please note
The power supply for the inputs is provided via the AS-i
bus.
The Local control unit must always be provided with 24 V
separately via the load voltage connection(black flat
cable).
The AS-Interface has an integrated watchdog function
which resets the outputs in the event of failure of the bus
communication.
1
0 V
2
+24 V
3
AS-i – (light blue)
4
AS-i + (brown)
24V DC
BUS
1
2
3
4
Fig. 3/29: Assignment of the AS-Interface connections