5. Diagnostics and error handling
5-11
Festo P.BE-CPX-FVDA-P2-EN en 1209NH English
5.3.2
Behaviour in the event of an error
Status
LED
FP-
LED
Chan-
nel er-
ror LED
Module
error
LED
Error
no.
Error description
2
2)
Short circuit/overload at the output
Error
elimina-
tion
sec-
tion 5.2
3
3)
Wire break
5
1)
Undervoltage in the supply voltage
61
1)
Overvoltage of the supply voltage
65
1)
The PROFIsafe address set by the
DIL switch does not agree with the
setting on the PROFIsafe master
(F_DEST_ADD).
66
1)
Error in safe communication.
67
1)
Timeout in the PROFIsafe
transmission.
68
2)
Cross circuit error (bypass circuit
error) at the output
69
1)
Error in safe parameterisation
(safety parameterisation invalid).
The PROFIsafe communication
cannot be constructed.
4)
145
1)
Module has established an error in
the self-test.
1)
All output channels of the module are passivated (CH0 ... CH2 are switched off).
2)
If “channel-wise passivation” is active, only the affected output channel is passivated.
Otherwise
1)
.
3)
Does not result in safety switch-off.
4)
In many cases, channel-error LEDs are also illuminated.
Tab. 5/7:
Behaviour in the event of an error
Summary of Contents for 1971599
Page 2: ......
Page 75: ...Installation 2 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 2 Installation...
Page 91: ...Commissioning 3 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 3 Commissioning...
Page 112: ...3 Commissioning 3 22 Festo P BE CPX FVDA P2 EN en 1209NH English...
Page 113: ...Operation 4 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 4 Operation...
Page 143: ...Index B 1 Festo P BE CPX FVDA P2 EN en 1209NH English Appendix B Index...
Page 144: ...B Index B 2 Festo P BE CPX FVDA P2 EN en 1209NH English Table of contents B Index B 1...
Page 150: ...B Index B 8 Festo P BE CPX FVDA P2 EN en 1209NH English W Wire break 3 12 5 4...