3. Commissioning
3-11
Festo P.BE-CPX-FVDA-P2-EN en 1209NH English
Module parameters: general diagnostics
Operator unit
Function no.
4828 + m * 64 +
6
m = module number (0 ... 47)
Description
This parameter influences the general diagnostic behaviour of the module.
It determines whether channel-, module- or protocol-specific error messages
should be suppressed or reported.
Active diagnostics cause the following. The corresponding error is:
– sent to the CPX bus node
– displayed using the module error LED.
Observe the exceptions named under the note.
Bit
General diagnostics
Bit 0:
output channel 0
Bit 1:
output channel 1
Bit 2:
output channel 2
Bit 3:
reserved
Bit 4:
module
Bit 5:
failsafe protocol
Bit 6, 7:
reserved
[General diagnosis]
[Channel 0]
[Channel 1]
[Channel 2]
[Module]
[Failsafe protocol]
Values
0 = inactive – suppress error message
1 = active – report error (presetting)
[Inactive]
[Active]
Note
Exceptions:
– Error messages regarding wire break can
not
be influenced with this paramet-
er. But the wire break monitoring function can be activated or deactivated with
the monitoring wire break parameter (
Tab. 3/7).
– With module-specific error messages, diagnostic messages from the failsafe
protocol are
not
suppressed.
Tab. 3/6:
General diagnostics
Module parameter: Monitoring wire break
Operator unit
Function no.
4828 + m * 64 +
7
m = module number (0 ... 47)
Description
Establishes whether the respective output channel should be monitored for wire
break.
Deactivating the wire break monitoring is necessary if:
– a load smaller than the minimum-specified load is to be switched or
– the electrical signal is guided additionally through external relays that them-
selves disconnect the circuit.
Summary of Contents for 1971599
Page 2: ......
Page 75: ...Installation 2 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 2 Installation...
Page 91: ...Commissioning 3 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 3 Commissioning...
Page 112: ...3 Commissioning 3 22 Festo P BE CPX FVDA P2 EN en 1209NH English...
Page 113: ...Operation 4 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 4 Operation...