2. Installation
2-10
Festo P.BE-CPX-FVDA-P2-EN en 1209NH English
2.4
Set PROFIsafe address
The output module is controlled by an F-Host via PROFIsafe
and requires a PROFIsafe address for unique identification.
The PROFIsafe address is determined through configuration
software and also set binary coded directly at the output
module with the 10-element DIL switch. Both settings must
match.
The 10-element DIL switch is located directly on the electron-
ics module and can be set with a dismantled connection block
(
Fig. 1/2).
Permissible are PROFIsafe addresses from 1 to 1023.
The DIL switch setting is evaluated in the run-up phase of the
firmware. For that reason, the output module must be restar-
ted to accept the changed address through a new switch-on
of the load voltage U
VAL
! Information on address allocation by
configuration software can be found in the documentation of
the software used.
Note
Incorrect handling can cause damage to the electronics
modules.
•
Never push/pull the electronics module into/out of the
interlinking block when powered.
Electronics modules include electrostatically sensitive
devices.
•
Observe the handling specifications for electrostatically
sensitive devices.
•
Discharge yourself from static discharges before assem-
bling or disassembling modules to protect the modules.
Summary of Contents for 1971599
Page 2: ......
Page 75: ...Installation 2 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 2 Installation...
Page 91: ...Commissioning 3 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 3 Commissioning...
Page 112: ...3 Commissioning 3 22 Festo P BE CPX FVDA P2 EN en 1209NH English...
Page 113: ...Operation 4 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 4 Operation...
Page 143: ...Index B 1 Festo P BE CPX FVDA P2 EN en 1209NH English Appendix B Index...
Page 144: ...B Index B 2 Festo P BE CPX FVDA P2 EN en 1209NH English Table of contents B Index B 1...
Page 150: ...B Index B 8 Festo P BE CPX FVDA P2 EN en 1209NH English W Wire break 3 12 5 4...