1. System overview CPX-FVDA-P2
1-30
Festo P.BE-CPX-FVDA-P2-EN en 1209NH English
Example 3 – permissible use of the CPX-FVDA-P2
Connection of safety relays to one of the two output channels
CH1 or CH2.
2
1
3
0 V
VAL
24 V
VAL
M CH1/2
P CH1/2
0 V CH1/2
+24 V CH1/2
1
Output channel CH1 or CH2 of the
output module CPX-FVDA-P2
2
Safety relay 1 with forced feedback
contact
3
Safety relay 2 with forced feedback
contact
Fig. 1/10: Safe connection of safety relays