Contents and general instructions
XV
Festo P.BE-CPX-FVDA-P2-EN en 1209NH English
Attainable safety level
With the CPX-FVDA-P2, safety functions can be implemented
up to:
–
safety integrity level SIL 3 in accordance with IEC 61508
–
performance level e, cat. 3 in accordance with
EN ISO 13849-1.
The CPX-FVDA-P2 achieves an SIL performance limit of max.
SIL CL3 in accordance with EN 62061.
The attainable safety level of the entire safety system de-
pends on other components used to implement the safety
function.
To maintain the safety level:
•
Check the operational capability of the safety equipment
at adequate intervals.
Failures due to common cause (common cause failure – CCF)
Common cause failures cause the loss of the safety function,
since both channels (P and M) in a two-channel system fail
simultaneously.
Through the following measures, you ensure that common
cause failures are avoided:
–
Observe operating voltage limits
–
Comply with temperature range
–
Use max. 2 output channels in a shared safety-oriented
control circuit
Additional measures for avoidance of common cause faults
may result from the application.
Summary of Contents for 1971599
Page 2: ......
Page 75: ...Installation 2 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 2 Installation...
Page 91: ...Commissioning 3 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 3 Commissioning...
Page 112: ...3 Commissioning 3 22 Festo P BE CPX FVDA P2 EN en 1209NH English...
Page 113: ...Operation 4 1 Festo P BE CPX FVDA P2 EN en 1209NH English Chapter 4 Operation...
Page 143: ...Index B 1 Festo P BE CPX FVDA P2 EN en 1209NH English Appendix B Index...
Page 144: ...B Index B 2 Festo P BE CPX FVDA P2 EN en 1209NH English Table of contents B Index B 1...
Page 150: ...B Index B 8 Festo P BE CPX FVDA P2 EN en 1209NH English W Wire break 3 12 5 4...