2. Installation
2-12
Festo P.BE-CPX-FVDA-P2-EN en 1209NH English
This is how you set the PROFIsafe address at the DIL switch:
Note
Incorrect handling can cause damage to the electronics
modules.
•
First switch off the supply voltage before conducting any
mounting or installation work.
•
Only switch on the electrical supply voltage when the
product has been fully assembled and all of the installa-
tion work is complete.
1. Switch off the power supplies for the CPX terminal.
2. Remove the mounted connection block (
section 2.5.1).
3. Carefully set the desired PROFIsafe address at the DIL
switch with a suitable tool, e.g. a small watchmaker’s
screwdriver.
When mounting, observe the instruction in section 2.5.2
(threaded connector without distortion, clean connection
surfaces, etc.).
4. Remount the connection block. Tightening torque
Technical data (appendix A.1).