OMNI-400/OMNI-400EU and OMNI-600/OMNI-600EU Installation and Setup Guide
6-14
Q 07, L2/L4: CS Receiver Type —
Enter the L2 and L4 digits for the desired receiver type from the
table below (checkmark indicates the option is selected).
L2/L4
Entry
FORMAT PULSE SPEED
HANDSHAKE FREQUENCY
Digit*
10 PPS
20 PPS
40 PPS
1400 HZ
2300 HZ
PARITY
TYPICAL CS RECEIVER
0
✔
✔
FBII, ADEMCO, SILENT KNIGHT
1
✔
✔
FBII, ADEMCO, RADIONICS
2
✔
✔
FBII
4
✔
✔
FBII, SILENT KNIGHT
5
✔
✔
FBII, RADIONICS
6
✔
✔
FBII, RADIONICS
8
✔
✔
✔
FBII
9
✔
✔
✔
FBII
A
✔
✔
✔
FBII
C
✔
✔
✔
FBII
D
✔
✔
✔
FBII, RADIONICS
E
✔
✔
✔
FBII, RADIONICS
*NOTE:
The system will ignore the value placed in this digit if it is transmitting in one of the DTMF formats
(FBII Superfast, ADEMCO PID, ADEMCO Express). For UL installations, the acceptable receivers are
FBII CP220 (all formats except ADEMCO Express, 4x1 + 4x2, and ADEMCO High Speed), ADEMCO
685 (all formats without parity and not FBII Superfast), and Silent Knight 9000 (10PPS, No Parity,
1400 or 2300Hz).
QUESTION 08 REPORTING OPTIONS
L1 L2 L3 L4
This question defines the reporting options. Enter the digits as follows:
Q 08, L1 —
Enter the L1 digit for the desired reporting options from the table below.
Report Type
L1
Entry
Backup Dual Split Disabled
Report Stay
Bypass
0
✔
1
✔
2
✔
3
✔
4
✔
✔
5
✔
✔
6
✔
✔
Backup: The system first dials central
station 1. If dialing fails, the system will
dial central station 2 (if programmed). If
dialing fails again, the system will begin
alternating dialing between central
station 1 and central station 2 until
contact is established or the maximum
number of dialing attempts (see Question
08, Location 3) expires.
Dual: Events will be sent to both central station phone numbers.
Split Reporting: If split reporting is enabled, then all reports other than openings and closings will be
sent to CS#1. Openings/closings will be transmitted to CS#2.
Dialer Disable: This option will turn OFF the digital dialer, making the control a local panel. The
Dialer Disable selection shall not be selected for UL installations.