OMNI-400/OMNI-400EU and OMNI-600/OMNI-600EU Installation and Setup Guide
6-26
Q 14, L4 —
Enter the L4 digit for the desired events that will cause reports to be sent to a pager.
L4
Entry
Zone
Alarm
Zone
Trouble
User
Open
User
Close
0
1
✔
2
✔
3
✔
✔
4
✔
5
✔
✔
6
✔
✔
7
✔
✔
✔
8
✔
9
✔
✔
A
✔
✔
B
✔
✔
✔
C
✔
✔
D
✔
✔
✔
E
✔
✔
✔
F
✔
✔
✔
✔
Zone Alarm/Zone Trouble: Upon an alarm or
trouble, a message is sent to the system’s pager
number. Only one event is reported at a time.
User Open/User Close: This enables system-wide
open and/or close pager reports.
QUESTION 15 BELL TIMEOUT/AC DELAY/RING COUNT
L1 L2 L3 L4
Burg bell Fire bell AC dial
ring
timeout timeout delay count
Q 15, L1/L2: Burglary Bell/Fire Bell Timeout —
Enter the L1 and L2 digits for the desired burglary and
fire bell/siren timeouts, respectively, from the table below.
Entry
BURGLARY & FIRE
BELL TIMEOUTS
Entry
BURGLARY & FIRE
BELL TIMEOUTS
1
3 minutes
9
27 minutes
2
6 minutes
A
30 minutes
3
9 minutes
B
33 minutes
4
12 minutes
C
36 minutes
5
15 minutes
D
39 minutes
UL
Must be programmed as
“2” for UL installations.
6
18 minutes
E
42 minutes
7
21 minutes
F
Infinite
8
24 minutes
Q 15, L3: AC Dial Delay —
AC loss reporting time may be delayed in 15-minute increments for values
1–F. Zero selects random delay, which can be anywhere between 10 and 225 minutes. Enter AC loss
dial delay from the table below.