SFC
Functions
4.
89
Control direction
Meaning:
Direction of the control
Display:
Direct/inverse (e.g. for pH)
Explanation:
Defines which medium is used to perform the correction.
Example:
pH:
Control direction "inverse": Lowering pH-value by
adding acid
pH:
Control direction "direct": Adding alkaline to raise
the pH value
Setpoint
Specified value at which the control variable can be maintained by
the controller. The setting range corresponds to the respective
measuring range.
Control variable 2
This parameter activates and deactivates a second control
variable during the single feed forward (only with application 2).
If „Control Variable 2“ = measured value X is selected, this
influences the actuator output. The „Off“ setting indicates that this
control variable is inactive (factory setting) (see 4.5.2.1 “Single
feed forward with process measurement”).
T
Sampling time T is the time after which a change controlvariable or
setpoint is responded to. This value must be adjusted in the case
of delayed feedback signals.
Tconst
Defines the constant dead time in the compound loop. Consists of
the sample water line dead time and the dosing delay time (for the
calculation, see 4.5.2.3 “Compound loop with process
measurement”).
Tn
Meaning:
Integral action time (I-element)
Display:
Minutes (min)
Explanation:
On the basis of the integral action time Tn, the dosing capacity
changes constantly until the setpoint is reached. The higher the
value of Tn, the longer it takes until the controller increases the
dosing rate.
Tn higher: Control response becomes slower
Tn lower: Control response is faster
Setting range:
The parameter Tn can be set from 0 – 100 min (Tn = 0 means that
the "I-element" is deactivated, i.e. a pure P-control response
applies). It may not be possible to reach the setpoint value.
Summary of Contents for WALLACE & TIERNAN SFC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC from version V 3 08 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 590 000 DE IM 0719 SFC Please note Original instruction manual...
Page 40: ...40 WT 050 590 000 DE IM 0719 Description SFC 3...
Page 118: ...118 WT 050 590 000 DE IM 0719 Functions SFC 4...
Page 121: ...SFC Installation 5 121 Top hat rail assembly...
Page 122: ...122 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 123: ...SFC Installation 5 123 Top hat rail assembly...
Page 124: ...124 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 125: ...SFC Installation 5 125 Control cabinet installation assembly...
Page 126: ...126 WT 050 590 000 DE IM 0719 Installation SFC 5 Control cabinet installation assembly...
Page 127: ...SFC Installation 5 127 Installation of the front panel on the control cabinet...
Page 156: ...156 WT 050 590 000 DE IM 0719 Installation SFC 5...
Page 218: ...218 WT 050 590 000 DE IM 0719 Operation SFC 6...
Page 232: ...232 WT 050 590 000 DE IM 0719 Maintenance SFC 7...
Page 266: ...266 WT 050 590 000 DE IM 0719 Complete Units Retrofit Kits and Spare Parts SFC 8...
Page 274: ...274 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 275: ...SFC Declarations and certificates 10 275 10 2 Certificate of Compliance...
Page 276: ...276 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 284: ...284 WT 050 590 000 DE IM 0719 Settings Table SFC 11...