Completing
adaption without errors
When the loop times (dead time Tu and rise time Ts) have been
completed without error, calculation of the control parameters Xp
and Tn commences. This is indicated by the message "Adaption
OK". The calculated parameters are entered in the menus. When
adaption has been concluded, the measuring amplifier adjusts
with the newly calculated control parameters and continues in the
selected operating mode (e.g. automatic).
To monitor the determined loop times they are entered into the
"Tu" and "Ts" menus .
If errors occur in the control loop during adaption, incorrect loop
times and therefore incorrect control parameters can be
determined.
Caution!
The remaining control parameters Ymin, Ymax and Tp are not
influenced when adaption is performed. The control parameters
Xp and Tn are determined for Ymin = 0 % (no basic load) and
Ymax = 100 % (no dosing rate limitation). If there is a system-
specific requirement for a basic load Ymin or a dosing rate
limitation Ymax, it must be taken into account that the control loop
is restricted as a result. There is then the risk of excessive
chlorination (Ymin too high) or inadequate chlorination (Ymax
limits excessively).
Completing
adaption with error
If errors occur in the control loop during adaption (e.g. filter
backwashing, changes in the circulation or widely fluctuating
number of visitors to the pool) or if the reaction times of the control
loop are too long, adaption is interrupted.
Possible error conditions:
Initial value not reached (Display: "T = >8h")
When adaption has started and the dosing system has closed or
the dosing pump has switched off, the measuring amplifier waits
until the actual value has dropped below the initial value (0.2 x the
measurement range value). This delay is indicated by the
message "2: X = 20 %" and the maximum permissible time is 8
hours.
Loop dead time too high (Display: "Tu = > 1h")
The value determined by the time measurement between starting
up the dosing, switching on the dosing pumps and the rise of the
actual value may only take a maximum of 1 hour. This measured
time is displayed by "6: Tu!".
Summary of Contents for WALLACE & TIERNAN SFC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC from version V 3 08 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 590 000 DE IM 0719 SFC Please note Original instruction manual...
Page 40: ...40 WT 050 590 000 DE IM 0719 Description SFC 3...
Page 118: ...118 WT 050 590 000 DE IM 0719 Functions SFC 4...
Page 121: ...SFC Installation 5 121 Top hat rail assembly...
Page 122: ...122 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 123: ...SFC Installation 5 123 Top hat rail assembly...
Page 124: ...124 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 125: ...SFC Installation 5 125 Control cabinet installation assembly...
Page 126: ...126 WT 050 590 000 DE IM 0719 Installation SFC 5 Control cabinet installation assembly...
Page 127: ...SFC Installation 5 127 Installation of the front panel on the control cabinet...
Page 156: ...156 WT 050 590 000 DE IM 0719 Installation SFC 5...
Page 218: ...218 WT 050 590 000 DE IM 0719 Operation SFC 6...
Page 232: ...232 WT 050 590 000 DE IM 0719 Maintenance SFC 7...
Page 266: ...266 WT 050 590 000 DE IM 0719 Complete Units Retrofit Kits and Spare Parts SFC 8...
Page 274: ...274 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 275: ...SFC Declarations and certificates 10 275 10 2 Certificate of Compliance...
Page 276: ...276 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 284: ...284 WT 050 590 000 DE IM 0719 Settings Table SFC 11...