72
WT.050.590.000.DE.IM.0719
Functions
SFC
4.
Please note
If the measuring range end value of the flow meter is not identical
with the actual maximum flow rate, a factor for adjusting the flow
rate signal should be input in the menu „Inputs/Outputs“ - „Flow
Wq“.
For example:
Measuring range flow meter = 5000 l/h / max. flow rate = 2500 l/h
=> factor = 5000: 2500 = 2,0
The ratio between control variable and dosing output is
determined by the internal dosing factor (control
„Dos.Fact.Source“ = internal), or it can also be set by an external
mA/V input signal (Dos.Fact.Source = external).
You can switch between internal and external dosing factor (DF)
via the digital input ("Dos.Fact.Source" = "external with DI2" or
"internal with DI2").
It is possible that a second control variable „Measured Value X“
(measured value from module 1) will have a proportional or inverse
proportional influence on the single feed forward ("X-direction" =
direct / inverse variable).
The second control variable X is activated, if the parameter
“Control Variable2“ is set to "Measured Value X" (second control
variable deactivated by the „Off“ setting (factory setting).
The amplification factor for this parameter is defined by the X-
factor input parameter.
The controller output is calculated in this operating mode as
follows:
Yout = Wq x DF x (X-measured value x X-factor) x Yout-factor
Wq
Control variable 1 flow rate in %
DF
set dosing factor in %
X-measured value Control variable 2 measured value sensor measuring
module 1 in %
X factor
Amplification factor for X measured value
Yout
Determined controller output value %
Yout factor
This factor gives the option of increasing the dosing
output by a dosing factor DF of 100 % when the
setpoint value is not reached, increase the dosing
output.
Setting range: 1.0– 4.0
Factory setting: 1.0
Please note
If this factor is increased, there is a danger that the setpoint value
will also not be reached with a higher flow rate value, because the
Yout value takes the value 100 % prematurely.
Summary of Contents for WALLACE & TIERNAN SFC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC from version V 3 08 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 590 000 DE IM 0719 SFC Please note Original instruction manual...
Page 40: ...40 WT 050 590 000 DE IM 0719 Description SFC 3...
Page 118: ...118 WT 050 590 000 DE IM 0719 Functions SFC 4...
Page 121: ...SFC Installation 5 121 Top hat rail assembly...
Page 122: ...122 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 123: ...SFC Installation 5 123 Top hat rail assembly...
Page 124: ...124 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 125: ...SFC Installation 5 125 Control cabinet installation assembly...
Page 126: ...126 WT 050 590 000 DE IM 0719 Installation SFC 5 Control cabinet installation assembly...
Page 127: ...SFC Installation 5 127 Installation of the front panel on the control cabinet...
Page 156: ...156 WT 050 590 000 DE IM 0719 Installation SFC 5...
Page 218: ...218 WT 050 590 000 DE IM 0719 Operation SFC 6...
Page 232: ...232 WT 050 590 000 DE IM 0719 Maintenance SFC 7...
Page 266: ...266 WT 050 590 000 DE IM 0719 Complete Units Retrofit Kits and Spare Parts SFC 8...
Page 274: ...274 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 275: ...SFC Declarations and certificates 10 275 10 2 Certificate of Compliance...
Page 276: ...276 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 284: ...284 WT 050 590 000 DE IM 0719 Settings Table SFC 11...