Functions
SFC
4.
Calculation 3:
The sample water distraction is carried out as in calculation 1 and/
or 2. To increase the exposure time, the sample water is also sent
through a delay tank.
The exposure time in the delay tank must be added to the
calculated time.
Determining the dosing dead
time (dosing delay)
Dosing dead times arise from long dosing lines and positioner
running times.
Calculation 1:
Determining the dead time based on dosing line length
The dosing dead time can be determined as follows:
t
dos
= (4.71 x d
dos
x d
dos
x l
dos
) : Q
dos
(result in min)
d
dos
= Internal diameter of the dosing line in cm
I
dos
=
Length of the dosing line in m
Q
dos
= Dosing line flow rate in l/h
Calculation 2:
If rapid control variable changes are expected in the system, which
the dosing equipment cannot adjust to (e.g. positioner running
times, dosing pump cycle times), the dosing delay time should be
assumed under all circumstances to be half of the positioner
running time ty or the cycle time tp.
At a positioner running time of 80 seconds, a value of approx. 40
s should be assumed as the constant dosing delay.
The sum of the measured dead time and the dosing delay is
displayed in the< Tconst > menu in minutes.
Determining the control variable
dependent Tvar dead time
The control variable dependent Tvar dead time depends on the
nominal flow rate, the internal diameter of the line and the distance
between where the chlorine is added and the sample water
extracted.
t
var
= (d
pipe
x d
pipe
x l
pipe
) : (212,3 x Q
nom
) (result in min)
d
pipe
=
Internal diameter of the pipeline in cm
l
pipe
=
Distance between where chlorine is added and
sample water extracted in m
Q
nom
=
Nominal flow rate in m³/h (reflects the flow rate,
which is preset for the controller as 100% flow signal)
If there are special reaction tanks in the system, they must be
treated separately.
Summary of Contents for WALLACE & TIERNAN SFC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC from version V 3 08 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 590 000 DE IM 0719 SFC Please note Original instruction manual...
Page 40: ...40 WT 050 590 000 DE IM 0719 Description SFC 3...
Page 118: ...118 WT 050 590 000 DE IM 0719 Functions SFC 4...
Page 121: ...SFC Installation 5 121 Top hat rail assembly...
Page 122: ...122 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 123: ...SFC Installation 5 123 Top hat rail assembly...
Page 124: ...124 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 125: ...SFC Installation 5 125 Control cabinet installation assembly...
Page 126: ...126 WT 050 590 000 DE IM 0719 Installation SFC 5 Control cabinet installation assembly...
Page 127: ...SFC Installation 5 127 Installation of the front panel on the control cabinet...
Page 156: ...156 WT 050 590 000 DE IM 0719 Installation SFC 5...
Page 218: ...218 WT 050 590 000 DE IM 0719 Operation SFC 6...
Page 232: ...232 WT 050 590 000 DE IM 0719 Maintenance SFC 7...
Page 266: ...266 WT 050 590 000 DE IM 0719 Complete Units Retrofit Kits and Spare Parts SFC 8...
Page 274: ...274 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 275: ...SFC Declarations and certificates 10 275 10 2 Certificate of Compliance...
Page 276: ...276 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 284: ...284 WT 050 590 000 DE IM 0719 Settings Table SFC 11...