Gammapilot M FMG60 FOUNDATION Fieldbus
Commissioning
Hauser
71
Range of values
optimum value
minimum value
maximum value
Value full (*14)
100%
60%
100%
Value empty (*17)
0%
0%
40%
"Calibration" (*15)
Local display
Calibration *15
Stop/edit
Start
This function is used to start automatic entry of the selected calibration point
Options:
•
Stop/edit
This option must be selected if:
– The calibration point is not to be entered (e.g. because it has already been entered).
The pulse rate of the calibration point is then displayed in the following function
"Full
calibration" (*16)
or
"Empty calibration" (*18)
. This value can be changed if
required.
– The calibration point is to be entered manually. The Gammapilot M changes to the
"Full calibration" (*16)
or
"Empty calibration" (*18)
function.
•
Start
This option is used to start automatic entry of the calibration point. The Gammapilot M
then changes to the
"Avg. pulse rate" (*11)
function.
"Avg. pulse rate" (*11)
Local display
Avg. pulse rate *11
2548 cps
The average (integrated) pulse rate is displayed in this function (after the selection of
"Start" in the previous function). Initially, this value fluctuates (because of the decay
statistics), but reaches an average value over time due to integration. The longer the
averaging is performed, the lower the fluctuations.
c/s
t
"E"
A0018118
9
The integrated (average) pulse rate fluctuates greatly at the start. An average value is reached over time.
When the value is sufficiently stable users can quit the function by pressing . After this,
the Gammapilot M changes to the
"Calibration" (*15)
function. Here the
"Stop/edit"