Wiring
Gammapilot M FMG60 FOUNDATION Fieldbus
32
Hauser
5.9
Wiring in connection compartment 2
L
CAUTION
Note the following before connecting:
‣
Connect the potential matching line to the external ground terminal of the transmitter
and to the ground terminal of the water cooling jacket (if present) before connecting
‣
The cables must be adequately insulated, with due consideration given to the supply
voltage and the overvoltage category.
‣
The connecting cables must offer adequate temperature stability, with due
consideration given to the ambient temperature.
+
-
PT100
IN CASCADE OUT
SIM WP
OFF
ON
3
4
5
6
7
8
9 10 11 12
+ - - +
0
13
2
A0019827
1. Unscrew the cover
2. Push the following cables through the corresponding cable glands or cable entries:
signal cable (if the signal output is located in connection compartment 2), Pt100
cable (if present), cascading cable (input and/or output, if required)
3. Wire up according to the terminal assignment diagram
4. Tighten the cable glands or cable entries so that they are leak-tight
5. Screw the cover securely back onto the connection compartment
5.10 Connecting the remote display and operating unit
FHX40
The remote display and operating unit FHX40 is available as an accessory. It is connected
to the FHX40 connector of the Gammapilot M via the cable supplied. The housing of the
Gammapilot M does not have to be opened for this.